A-1. CL-201-E DCON Command Sets
- 90 -
Command
Description
@AAEATCN
Enable AI alarm of a channel, N = 0 for CO, 1 for relative humidity, 2
for temperature in 0.01°C, 3 for temperature in 0.01°F, 4 for dew
point temperature in 0.01°C, 5 for dew point temperature in 0.01°F
T->M: momentary alarm, L: latched alarm
@AAHI(data)CN
Set high alarm limit of an AI channel, N = 0 for CO in 1ppm, 1 for
relative humidity in 0.01%, 2 for temperature in 0.01°C, 3 for
temperature in 0.01°F, 4 for dew point temperature in 0.01°C, 5 for
dew point temperature in 0.01°F
@AAHO
Read humidity offset
@AAHO(data)
Set humidity offset, data in format of -100.00 ~ +100.00
@AALO(data)CN Set low alarm limit of an AI channel, N = 1 for relative humidity in
0.01%, 2 for temperature in 0.01°C, 3 for temperature in 0.01°F, 4
for dew point temperature in 0.01°C, 5 for dew point temperature in
0.01°F
@AARACN
Read AI alarm enabled/disabled status of a channel
response
!AAN, N->0: disabled, 1: momentary, 2: latched
@AARAO
Read AI alarm status
response
!AAHHLL
@AARH
Read all high latched values of analog input channels
@AARHN
Read channel high latched value of analog input
@AARHCN
Read high alarm limit of an AI channel
@AARL
Read all low latched values of analog input channels
@AARLN
Read channel low latched value of analog input
@AARLCN
Read low alarm limit of an AI channel
@AART
Read RTC data
response
!AAYYYYMMDDHHMMSS
@AARTYYYYMM
DDHHMMSS
Set RTC data
@AATO
Read temperature offset in 0.01°C
@AATO(data)
Set temperature offset in 0.01°C, -100.00 ~ +100.00
~**
clear host watchdog timeout counter
~AA0
read host watchdog status
~AA1
clear host watchdog timeout status
~AA2
read host watchdog enable/disable status and timeout value