C-6. CL-206-E Modbus Address Mappings (Base 1)
- 184 -
Address Description
Attribute
40932
The first fan off period in a day, ending minute, 0 ~ 59
R/W
40933 ~
40936
The second fan off period in a day
R/W
40937 ~
40940
The third fan off period in a day
R/W
40941 ~
40944
The fourth fan off period in a day
R/W
40945 ~
40948
The fifth fan off period in a day
R/W
40949 ~
40952
The sixth fan off period in a day
R/W
00001
Digital output value of channel 0
R/W
00129
Safe value of digital output channel 0
R/W
00161
Power on value of digital output channel 0
R/W
00227
Write 1 to reload default TCP settings
Only for Modbus TCP protocol
W
00234
Write 1 to reboot module
Only for Modbus TCP protocol
W
00257
RS-485 Protocol, 0: DCON, 1: Modbus RTU
Only for Modbus RTU protocol
R/W
00260
Modbus RTU host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear host watchdog timeout
status
Only for Modbus RTU protocol
R/W
00261
RS-485 host watchdog mode, 1: enable, 0: disable.
Only for Modbus RTU protocol
R/W
00262
Write 1 to play notification sound
W
00270
Host watch dog timeout status, write 1 to clear host watch dog
timeout status
Only for Modbus RTU protocol
R/W
00273
Reset status, 1: first read after powered on, 0: not the first read
after powered on
Only for Modbus RTU protocol
R
00279
Fan control, 0: off, 1: on
R/W
00280
Write 1 to clear all high latched analog input values
W
00281
Write 1 to clear all low latched analog input values
W