A-5. CL-205-E DCON Command Sets
- 109 -
Command
Description
@AADLC
Read the data logger command
response
!AAh, 0: stop, 1: run, 2: run in period mode
@AADLCh
Set the data logger command, h->0: stop, 1: run, 2: run in period mode
@AADLE
Read the ending of the period setting of the data logger for period logging
mode
response
!AAyyyymmddhhmmss
@AADLEyyyymmd
dhhmmss
Set the ending of the period setting of the data logger for period logging
mode
yyyy: year, 2000 to 2199, mm: month, 01 to 12, dd: date, 01 to 31, hh:
hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to 59
@AADLN
Read number of log records in the data logger
response
!AAhhhhhhhh, hhhhhhhh in hex format
@AADLO
Read the overwriting mode when data logger is full
response
!AAh, 0: stop logging when full, 1: overwrite
@AADLOh
Set the overwriting mode when data logger is full
h->0: stop logging when full, 1: overwrite
@AADLP
Read the sampling period setting of the data logger
response
!AAhhmmss, hh: hour, 0 to 24, mm: minute, 0 to 59, ss: second, 0 to
59
@AADLPhhmmss
Set the sampling period setting of the data logger
@AADLS
Read logging status of the data logger
response
!AAhh, hh in hex format, 00: stopped, 01: running, others: error
@AADO0V
set DO, V-> 0: off, 1: on
@AAEATCN
Enable AI alarm of a channel, N = 0 for NH3, 1 for relative humidity, 2
for temperature in 0.01
°
C, 3 for temperature in 0.01
°
F, 4 for dew point
temperature in 0.01
°
C, 5 for dew point temperature in 0.01
°
F
T->M: momentary alarm, L: latched alarm