C-12. CL-213 / CL-213-E Modbus Address Mappings (Base 1)
- 217 -
Address Description
Attribute
40949 ~
40952
The sixth fan off period in a day
R/W
00001
Digital output value of channel 0
R/W
00129
Safe value of digital output channel 0
R/W
00161
Power on value of digital output channel 0
R/W
00227
Write 1 to reload default TCP settings
Only for Modbus TCP protocol
W
00234
Write 1 to reboot module
Only for Modbus TCP protocol
W
00257
RS-485 Protocol, 0: DCON, 1: Modbus RTU
R/W
00260
Modbus RTU host watchdog mode
0: same as I-7000
1: can use AO and DO command to clear host watchdog timeout
status
R/W
00261
RS-485 host watchdog mode, 1: enable, 0: disable.
R/W
00262
Write 1 to play notification sound
Only for CL-213-E
W
00270
Host watch dog timeout status, write 1 to clear host watch dog
timeout status
R/W
00273
Reset status,
1: first read after powered on,
0: not the first read after powered on
R
00279
Fan control, 0: off, 1: on
R/W
00280
Write 1 to clear all high latched analog input values
W
00281
Write 1 to clear all low latched analog input values
W
00292 ~
00296
Low alarm status of channel 3 to 7. Write 1 to clear low latched
alarm.
channel 3: relative humidity in 0.01%,
channel 4: temperature in 0.01°C,
channel 5: temperature in 0.01°F,
channel 6: dew point temperature in 0.01°C,
channel 7: dew point temperature in 0.01°F
R/W