Min | Max Flow Rates
Relay Selection Mode
Reset Flow Totalizer
Press + keys for 3 seconds to reset the
flow totalizer
.
Programming Relay Output
STEPS
DISPLAY
OPERATION
Home Screen
Con = n: OP2 Manual Reset (Press
STR
for 3 sec to reset)
CV < SV: Relay 2 on (OP2
on
)
CV < SV: Relay 2 off (OP2
off
)
Refer to
Relay Selection Mode
Below
Press to change
Press to save
(Hysteresis is a buffer around the programmed set point)
Time Delay
5
▶
Hysteresis
4
▶
OP2 Output
Pulse Control (Frequency)
2
▶
Pulse Relay
3
▶
Press and Hold
SET
1
▶
+
🕓
3 Sec.
ALT NO.
Description
ALt = 0
CV > SV ▶ ON: CV < SV - HyS ▶ OFF "Normally Closed Relay"
ALt = 1
CV < SV ▶ ON: CV > SV + HyS ▶ OFF "Normally Open Relay"
ALt = 2
SV + HyS > CV > SV - HyS ▶ ON: CV > SV + HyS or CV < SV - HyS ▶ OFF
ALt = 3
SV + HyS > CV > SV - HyS ▶ OFF: CV > SV + HyS or CV < SV - HyS ▶ ON
HyS = Hysteresis — Acts like a buffer ± around pulse output (measured in GPM)
CV: Current Value = Flow Rate | SV = Selected or Programmed Value
PIPE SIZE
GPM
LPM
½" | DN15
1.0 | 3.5
32 | 120
¾" | DN20
1.5 | 5
45 | 170
1" | DN25
2.5 | 9
79 | 300
1½" | DN40
6.5 | 25
225 | 850
2" | DN50
10.5 | 40
357 | 1350
PIPE SIZE
GPM
LPM
3" | DN80
24 | 90
739 | 2800
4" | DN100
33 | 125
1149 | 4350
6" | DN150
60 | 230
1997 | 7590
8" | DN200
82 | 315
2735 | 10395
TIF Series
Multi-Function Batching Paddle Wheel Flow Meter