Programming

Programming Frequency Pulse Relay Output

STEPS

DISPLAY

OPERATION

Home Screen

Factory Default: Lk = 10

  

Otherwise meter will enter 

Lockout Mode*

  

Press   / 

STR

 

 to change  

Press   to save

Ut.G = Gallons (Factory default)

Ut.L = Liters  |  Ut.KL = Kiloliters
Press   to change  
Press   to save

Enter K Factor Value
Refer to Page 6 for K-Factor Values

Factory Default — 4mA = 0, 20mA = 100** 

**This can be change to suit application

STEPS

DISPLAY

OPERATION

Home Screen

CV -

 Program Value of (Flow Rate) Pulse (NPN) Output 

Preset Value of Flow Rate

Change to a Value that meets your Flow Rate Pulse Output

 

SV -

 CV > SV ▶ Flow Rate Pulse Output ON

CV < SV ▶ Flow Rate Pulse Output OFF

CV -

 Program Value of Flow Totalizer Pulse (NPN) Output 

SV: Preset Value of Flow Total

 

SV -

 CV > SV ▶ Flow Rate Pulse Output ON

 

2000 Default

 can be changed to desired value. Refer to "Programming 

OP2 Output" for totalizer options

Flow Totalizer Pulse

 - (Step #2 - Next)

 

Transmitter Range

 

K Factor

4

 

Pasword

Flow Rate Pulse Output

Select/Save/Continue 

Move selection  left

Change digit value

 

 

Units of Flow

Flow Total Pulse Output

 

 

Press and Hold 

SET

Press and Hold 

SET

 

 

STR

 

TIF Series

Multi-Function Batching Paddle Wheel Flow Meter

6

23-0069

+

🕓

 

3 Sec.

+

🕓

 

3 Sec.

Summary of Contents for truflo TIF Series

Page 1: ...ent changes without prior notice Rotates 330 M12 Quick Connect M12 Keyed to Ensure Proper Connection Vibrant 2x 6 Digit LED Display Corrosion Resistant NEMA 4X Enclosure Simple Push button Programming True Union Design TIF Series Multi Function Batching Paddle Wheel Flow Meter 1 23 0069 ...

Page 2: ...during installation and service of Truflo products Pressurized System Warning Sensor may be under pressure Take caution to vent system prior to installation or removal Failure to do so may result in equipment damage and or serious injury WARNING General Information Function Description Specification Operating Voltage 10 30VDC Current Compensation 60mA max Control Communication RS 485 Modbus Transm...

Page 3: ...read of the sensor cap then turn the sensor until the alignment tab is seated in the fitting notch Ensure tab is parallel to flow direction Hand tighten DO NOT use tools Ensure meter is firmly in place Installation Very Important Lubricate O rings with silicone provided Using an alternating twisting motion carefully lower the sensor into the fitting Do Not Force See Fig 5 Ensure tab notch are para...

Page 4: ...minimum number of pipe diameters distance upstream and downstream of the flow sensor Installation Positions Flange 90º Downward Flow 2x 90º Elbow 90º Elbow Flow Upward Reducer Ball Valve Figure 1 Figure 2 Figure 3 Good if NO SEDIMENT present NOTE Maximum of solids 10 with particle size not exceeding 0 5mm cross section or length Good if NO AIR BUBBLES present Preferred installation if SEDIMENT or ...

Page 5: ...tor Combo 220 200 180 160 140 120 100 80 60 40 20 0 60 PVC PP PVDF 104 140 175 212 248 20 F C 40 60 80 100 120 15 2 psi bar 13 8 12 4 11 0 9 7 8 3 6 9 5 5 4 1 2 8 1 4 0 Note During system design the specifications of all components must be considered Non Shock The TIF Series is equipped with a zirconium ceramic rotor pin and 2 bushings The TIF Series also incorporates a contoured Low Drag paddle w...

Page 6: ...t Value of Flow Rate Change to a Value that meets your Flow Rate Pulse Output SV CV SV Flow Rate Pulse Output ON CV SV Flow Rate Pulse Output OFF CV Program Value of Flow Totalizer Pulse NPN Output SV Preset Value of Flow Total SV CV SV Flow Rate Pulse Output ON 2000 Default can be changed to desired value Refer to Programming OP2 Output for totalizer options Flow Totalizer Pulse Step 2 Next Trans...

Page 7: ... and Hold SET 1 3 Sec ALT NO Description ALt 0 CV SV ON CV SV HyS OFF Normally Closed Relay ALt 1 CV SV ON CV SV HyS OFF Normally Open Relay ALt 2 SV HyS CV SV HyS ON CV SV HyS or CV SV HyS OFF ALt 3 SV HyS CV SV HyS OFF CV SV HyS or CV SV HyS ON HyS Hysteresis Acts like a buffer around pulse output measured in GPM CV Current Value Flow Rate SV Selected or Programmed Value PIPE SIZE GPM LPM DN15 1...

Page 8: ...rox 50 07 GENTLY tap 08 Congratulations Replacement procedure is complete 09 Ensure holes are aligned Pull out 05 Insert new paddle in flow meter 06 GENTLY tap 02 Tap until pin is 50 out 02 Small Pin Paddle Pin Hole TIF Series Multi Function Batching Paddle Wheel Flow Meter 8 23 0069 ...

Page 9: ...ve 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilat...

Reviews: