7. Auxiliary Delay ON
– (0-30 minutes)
Set the delay time in minutes for auxiliary heat to be locked out after a call
for second stage . This extra savings feature is used to temporarily lock out
auxiliary heat devices, allowing just heat pump to try to satisfy heat call .
Press the
up
or
down
button to select .
Press
the
right
button to advance to the next screen .
8 .
Lockout
(0-8°, COOL-HEAT)
Select the number of degrees set temperature can be changed during keypad
lockout .
COOL-HEAT
lockout allows adjustment of the set temperatures to
the maximum heat set temperature selected in Step 9 and minimum cool set
temperature selected in Step 10 .
Note:
The mode cannot be changed when the thermostat is locked .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
9 .
Maximum Heat Setpoint
(45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
10 .
Minimum Cool Setpoint
(45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .