Remote Sensor Installation (Optional)
1 . Remove cover from remote sensor housing .
2 . Select an appropriate location for mounting the remote sensor .
3 . Mount remote sensor unit using hardware provided .
4 . Install two strand shielded wire between remote sensor and thermostat . Shielded wire must be used .
Do not
run remote sensor wire in conduit with other wires .
•
Wire 1
should run between the S1 terminal on the thermostat and the S1 terminal on the remote sensor
•
Wire 2
should run between the S2 terminal on the thermostat and the S2 terminal on the remote sensor
• Connect the shielding of the wire to the S2 terminal on the thermostat
5 . Configure the thermostat to operate with the remote indoor sensor (see Configuration Mode setting 13,
Page 13) or use it for an outdoor sensor .
Note:
Remote or outdoor sensor reading can be displayed by
simultaneously pressing the
Down
and
SYS
buttons .
Remote Sensor: (Shown: Optional ICM ACC-RT103 Remote Indoor Sensor;
for outdoor sensor, order ACC-OD103.)