Configuration Mode Settings
4 .
Staged Off Outputs
Select whether the outputs for heating and cooling are staged off independently
or are satisfied simultaneously .
1 = outputs staged off independently
0 = outputs off simultaneously
Press the
up
or
down
button to set .
Press the
right
button to advance to the next screen .
3 .
2
nd
Stage Temperature Differential
(1°F to 5°F) (0 .5°C to 2 .5°C)
Set the number of degrees between when stage 1 turns on and when
stage 2 turns on .
Press the
up
or
down
button to set differential value .
Press the
right
button to advance to the next screen .
2 .
1
st
Stage Temperature Differential
(1°F to 5°F) (0 .5°C to 2 .5°C)
Set the number of degrees between your “setpoint” temperature and your
“turn on” temperature .
Press the
up
or
down
button to set differential value .
Press the
right
button to advance to the next screen .
1 .
Temperature Scale
(F or C)
Choose Fahrenheit or Celsius .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
The setup screens for Configuration Mode are as follows: