Installing and Changing Batteries
For Battery Thermostat Operation
If your LCD is blank, or displaying
LO BAT
, the batteries are not installed or
need to be changed. We suggest you change the batteries at least once a year,
or whenever the
LO BAT
warning displays.
Remove the cover, and install the two “AAA” alkaline batteries into the battery
compartment. Proper battery installation is important! Make sure the positive
ends of the batteries match the positive terminals in the battery compartment.
For Hardwired Thermostat Operation
Batteries are not required when a common wire is connected to the C terminal of the
MP2010L
thermostat.
Configuration Mode
3. Press both the
LEFT
and
RIGHT
switches for 1 second while the
MP2010L
is in
OFF
mode.
Press the
RIGHT
switch to advance to the next screen.
Note:
Pressing the
LEFT
switch will return you to the previous screen.
The configuration mode is used to set the
MP2010L
to match your system.
To configure the
MP2010L
, perform the following steps:
1. Verify the
MP2010L
is in the
OFF
mode.
Slide the system switch to the center position until off mode displays.
2. Remove the cover of the thermostat by gently pulling near one of the
corners at the top of the thermostat.
Press the
up
or
down
button to change settings within each screen.
To exit configuration mode, press both the
LEFT
and
RIGHT
switches for 1 second or slide the mode
switch to heat or cool.
To exit configuration mode, press both the
LEFT
and
RIGHT
switches for 2 seconds or slide the
mode switch to heat or cool.
6.
Room Temperature Offset
(+9°F to -9°F) (+5°C to -5°C)
Adjust to calibrate displayed room temperature to match actual room
temperature
(must be adjusted before permanent lock)
.
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
3.
Heat Pump
and
Non-Heat Pump
– Set to heat pump, or non-heat pump
system. For heat pumps, there will be a compressor time delay for heating
and cooling.
• 1 = Heat pump system
• 0 = Non-heat pump system
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
2.
Temperature Differential
(1°F to 5°F) (1°C to 3°C) – Set the number
of degrees between your “setpoint” temperature and your “turn on”
temperature.
Press the
up
or
down
button to set differential value.
Press the
RIGHT
switch to advance to the next screen.
1.
Temperature Scale
(F or C) – Choose Fahrenheit or Celsius.
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
ONE-YEAR LIMITED WARRANTY
The Seller warrants its products against defects in material or workmanship for a period of one (1) year
from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a
non-case credit for the purchase prices of the goods which are provided to be defective. The warranty and
remedies set forth herein do not apply to any goods or parts thereof which have been subjected to misuse
including any use or application in violation of the Seller’s instructions, neglect, tampering, improper storage,
incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly
administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code
information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test
the product claimed to be defective. Items claimed to be defective and are determined by Seller to be non-
defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller’s sole liability
hereunder and is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated
in writing, Seller makes no warranty that the goods depicted or described herein are fit for any particular
purpose.
LIAF189
Patent No. 424,953 – Design
Patent No. 6,597,275 – Thermal Intrusion Barrier
7313 William Barry Blvd., North Syracuse, NY 13212
(
Toll Free
) 800-365-5525 (
Phone
) 315-233-5266 (
Fax
) 315-233-5276
www.icmcontrols.com
Operating Modes
OFF Mode
• In this mode, the thermostat will not turn on the heating or cooling devices (manual fan can operate)
•
OFF
mode is also used to access the configuration screens
Cool Mode
• In this mode, the thermostat controls the cooling system
Heat Mode
• In this mode, the thermostat controls the heating system
Troubleshooting
Symptom
Remedy
No display
Check for 24 VAC at thermostat; display is blank when 24 VAC
is not present or if batteries are completely discharged
System fan does not come on
properly
Verify wiring is correct, check Gas/Electric jumper position (see
Parts Diagram)
All thermostat buttons are
inoperative
Verify 24 VAC is present; unit locks out when 24 VAC is not
present with no batteries installed
No response with first button
press
First button press activates backlight only when back light is
configured “ON” (see Configuration Mode Setting 9)
Heat or Cool not working
RC/RH jumper must be installed on single transformer systems
For heat pumps, Non-HP jumper must be on HP pins
Thermostat turns on and off too
frequently
Adjust temperature differential
(see Configuration Mode Setting 2)
Fan runs continuously
Slide FAN switch to auto to turn fan off
#4 to #8 configuration screens
not available
Thermostat has the permanent lockout function activated
(see Lockout Feature and Configuration Mode Setting 8)
Heat or Cool not coming on
Verify wiring is correct, verify RC/RH jumper is in place (for
single transformer system)
Err or Erd on display
Abnormal Rate of Change (ARC) detected. Thermostat defaults
into lockout sequence. When normal operation resumes, error
message can be cleared with press of any button
on display
Replace batteries with two fresh “AAA” alkaline batteries
Problem not listed above
Press Reset button once*
* Reset Button Function
: Configuration settings are unchanged.
4.
Maximum Heat Setpoint
(45°F to 75°F) (7°C to 24°C)
Adjust to control the maximum heat set temperature allowed.
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
5.
Minimum Cool Setpoint
(70°F to 90°F) (21°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
7.
Placebo Feature
– Set point can be set to wide range but they will be
controlled to maximum heat set point and minimum cool set point.
0 = Feature OFF
1 = Feature ON
Press the
up
or
down
button to select.
Press the
RIGHT
switch to advance to the next screen.
9.
Back Light
– (0 or 1)
0 = Back light never on (best for long battery life)
1 = Back light on when button pressed
Press the
up
or
down
button to select.
ARC Detection Technology
This thermostat comes enabled with ICM Controls’ patent-pending Abnormal Rate of Change
(ARC) detection technology that helps deter tenants from attempting to “trick” the thermostat into a
false reading. Upon sensing an abnormal rise or drop in temperature, the thermostat operation will
automatically default into a lockout sequence. The display will show
Err
for an abnormal RISE in
temperature, or
Erd
for an abnormal DROP in temperature. When the thermostat returns to normal
operation, the error message can be cleared with the press of any button.
8.
Permanent Lock Screen
Hold up and down button until counter reaches 0 to permanently lock
configuration screens.
!!! VERY IMPORTANT !!!
Configuration screens #4 to #8 can’t be changed after they are permanently
locked. To reconfigure, a locked thermostat must be returned to ICM Controls
for reprogramming, which involves a fee.