General information
8
TECHNICAL DATA
ASX 200 ÷ 800(5 BAR)
DESCRIPTION
u.m.
ASX
200
300
400
500
600
800
Nominal power
kW
233
349
465
581
698
930
Thermal capacity
kW
258
387
516
645
774
1032
Efficiency at 100% (N.C.V.)
%
90,31
90,18
90,12
90,08
90,18
90,12
Hydraulic pressure drop
mbar
30
29
52
33
48
35
Rated pressure
bar
5
5
5
5
5
5
Total capacity
l
735
750
865
1095
1245
1535
Total weight
kg
1400
1600
1850
2200
2200
2600
Electric supply
Volt ~
230
230
230
230
230
230
Frequency
Hz
50
50
50
50
50
50
Insulation class
IP
IP55
IP55
IP55
IP55
IP55
IP55
Electric power
W
W.D.
W.D.
W.D.
W.D.
W.D.
W.D.
Allowed fuels
Methane - LPG - Diesel - Naphtha
ASX 1000 ÷ 3000(5 BAR)
DESCRIPTION
u.m.
ASX
1000
1200
1500
1750
2000
2500
3000
Nominal power
kW
1163
1395
1744
2035
2326
2907
3488
Thermal capacity
kW
1292
1550
1937
2260
2584
3229
3876
Efficiency at 100% (N.C.V.)
%
90,02
90,00
90,04
90,04
90,02
90,03
89,99
Hydraulic pressure drop
mbar
54
38
59
80
105
52
60
Rated pressure
bar
5
5
5
5
5
5
5
Total capacity
l
1765
2265
2875
3155
3605
4570
5450
Total weight
kg
3000
3400
4000
5500
7500
8500
9000
Electric supply
Volt ~
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
1/N~ 230
Frequency
Hz
50
50
50
50
50
50
50
Insulation class
IP
IP55
IP55
IP55
IP55
IP55
IP55
IP55
Electric power
W
W.D.
W.D.
W.D.
W.D.
W.D.
W.D.
W.D.
Allowed fuels
Methane - LPG - Diesel - Naphtha
Water delivery ΔT max 30°C.
Electric powers only for gas or diesel fuels.
Design data
Minimum/maximum temperature
-10°C / 158,9 °C
Minimum/maximum temperature
-10°C / 191,7 °C
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz