General information
12
BURNERS
The burners that can be installed on the
ASX
boilers must be CE marked according to European Directives:
–
Gas Directive 2009/142/EC
–
Electromagnetic Compatibility Directive 2014/30/EU
–
Low Voltage Directive 2014/35/EU
–
Machinery Directive 2006/42/EC (for liquid fuel burners)
Since the optimal operation of the boiler depends on the correct selection of the burner and its adjustment, find below some
points to take into account:
–
The burner to be combined with the boiler must be of two-stage or modulating type; so that excessive flow temperature
variations can be avoided.
–
The burner firing range must include the point of operation of the boiler (flow rate-back pressure in combustion chamber
considering also any resistance/draught of the smoke duct)
–
the length of the combustion head must be adequate to the penetration into the combustion chamber provided by ICI and
shown in the table
–
the length and shape of the flame must be suitable to the flame inversion combustion chambers. The burner manufacturers
have this information as they are required by certification.
Øb
P6
m
IMPORTANT
The gap between the mouthpiece and door must be filled with flame-resistant thermoceramic material.
Dimensions
u.m.
ASX
200
300
400
500
600
800
P6
mm
280-330
310-360
310-360
350-400
350-400
370-420
Øb
mm
180
225
225
280
280
280
Dimensions
u.m.
ASX
1000
1200
1500
1750
2000
2500
3000
H
mm
2170
2260
2490
2430
2610
2730
2880
P6
mm
370-420
370-420
420-470
420-470
480-530
480-530
480-530
Øb
mm
280
320
360
360
360
360
400
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz