Maintenance
36
4
Maintenance
Periodic maintenance is an obligation required by the safety Legislation and duration of the appliance, and it must only be
entrusted to professionally qualified personnel.
The frequency of the operations is shown in the specific paragraph.
m
IMPORTANT
Before performing any maintenance or cleaning:
–
disconnect the electrical power supply by placing the main switch of the system, of the control panel and of the burner,
if any, at "
OFF
"
–
close the fuel supply
–
use all Personal Protective Equipment required by current Standards and Legislation
–
wait for the generator and the system to cool down.
ROUTINE MAINTENANCE
Depending on the degree of pollution of the premises, clean the ventilation and/or the air conditioner (if present) filters and grilles
frequently
Every 2-3 months check for dust deposits inside the panel, vacuum and/or blow to eliminate any deposits
Every six months check the clamping of the connections to the inner components, paying particular attention to the power
circuits
Every six months check the clamping of the connections to the field control/safety devices, including any junction boxes
Annually check that the electrical panel, the generator and the control unit equipotential is properly connected to earth
Every 6 months, check the status of safety devices "(probes "and "pressure switches)
Carry out the maintenance of the burner (based on the relevant manufacturer’s instructions).
Check bolt tightening at the flanges and all seals/gaskets for wear.
Check the status of the internal coating of doors and fibreglass braided ropes.
Check the integrity of the flame indicator light.
Periodically clean furnace and tube bundle using a brush.
Check that turbulators, if any, are clean and not damaged.
Generally, gaseous fuels do not produce any carbon deposit, while the use of liquid fuels requires frequent cleaning to prevent
significant scale build-ups.
Check the wear of drain valves which tend to deteriorate more rapidly due to the sludge abrasive action.
Check the integrity of the electrical system on board the boiler.
Check the integrity of the control panel both externally (IP protection) and internally (check all the components inside the control
panel).
m
IMPORTANT
In order to preserve the proper operation of the generator over time, we recommend requesting a half-yearly/yearly
inspection by the Technical Assistance Service, for a general check of all parts.