background image

 

Reference: A938 

Index: B 

Page 16 

This document is the property of ICE SAS. It can not be reproduced or communicated to third parties without authorization. 

 

Instruction Manual – NPS914 Alarm and Indication IED 

I/O 

 

•  An object has Open and Close inputs which are used for indicating the status of the breaker on the 

HMI and in SCADA. Status can be indicated by any of the following: digital inputs, logical inputs or 
outputs. 

•  A withdrawable object has In and Out inputs. Status can be indicated by any of the following: digital 

inputs, logical inputs or outputs. 

•  Both "Object Ready" and "Synchrocheck" have status inputs. If synchrocheck or object ready is 

used these inputs need to be active for the relay to be able to give object closing command. 

•  Object Open and Close signals define which digital output is controlled.  

Operation settings 

•  Breaker traverse time: How long gap there can be between open and close status change before 

intermittent status is reported by the function. 

•  Max close and open pulse length: Defines the maximum length of open and close commands. If 

status has changed before max pulse length has elapsed, the pulse is cut short. 

•  Control termination timeout: If status of the object does not change during this time, open or close 

fail event is recorded. 

•  After the set delay, if the controlled object does not respond accordingly, the procedure is 

terminated and a fail message is issued. 

 

Control settings (Application) 

 

•  Object application close and open: Signal set to these points can be used to open and close the 

object. Controlling the object through this point does not follow local/remote status of the relay. 

 

Control settings (DI) 

 

•  Access level for Mimic control: determines the access level required to control Mimic (each level 

has its own password). By default, the access level is set to "Configurator". 

•  You can use digital inputs to control the object locally or remotely. Remote controlling via the bus is 

configured in the protocol level. 

 

 

Summary of Contents for NPS914

Page 1: ...eference A938 Index B Page 1 This document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED...

Page 2: ...SI RBI B 16 04 2021 Update HWE ACH Read these instructions carefully and inspect the equipment to become familiar with it before trying to install operate service or maintain it Electrical equipment s...

Page 3: ...re output control 70 6 3 Programmable control switch 75 7 System integration 76 7 1 Communication protocols 76 7 2 Analog fault registers 91 7 3 Real time measurements to communication 91 8 Connection...

Page 4: ...urrenttransformermodule DG Distributedgeneration DHCP DynamicHostConfigurationProtocol DI Digital input DO Digital output DOL Direct on line DT Definite time FF Fundamental frequency FFT FastFouriertr...

Page 5: ...s the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED SW Software TRMS Truerootmeansquare VT Volt...

Page 6: ...the specific application of the NPS914 alarm and indication relay For other NP900 series products please consult their respective devicemanuals NPS914 may be applied as a substation alarm sounder a s...

Page 7: ...1 1 Local panel structure 1 Four 4 default LEDs Power Error Start configurable and Trip configurable 2 Sixteen 16 freely configurable LEDs with programmable legend texts 3 Three 3 object control butto...

Page 8: ...eimage below is the mimic view you can move through these menus by pressing the left and right arrow buttons Please note that the available quick display carousel view might be different if you have c...

Page 9: ...to the following six 6 main configuration menus General Protection Control Communication Measurement Monitoring They are presented in the image below The available menus vary according to the device t...

Page 10: ...onf Displays the hardware configuration of the unit The hardware configuration is also printed on the sticker located on the side of the unit Timesync source 0 Internal 1 External NTP 2 External Seria...

Page 11: ...s no input after a period of time defined with this parameter the unit automatically returns to the default view If set to 0 s this feature is not in use LED test 0 1 Activated 0 Whenactivated allLEDs...

Page 12: ...uring the objects Objects setting the various control functions Control functions and configuring the inputs and outputs Device I O The available control functions depend on the model of the device in...

Page 13: ...ng group at will please note that Force SG change enable must be Enabled Usedsetting groups this settingallows theactivation ofsetting groupsSG1 SG8 onlyone group is active by default SG local select...

Page 14: ...larm and Indication IED Objects Figure 3 4 10 Objects submenu Each activated object is visible in the Objects submenu By default all objects are disabled unless specifically activated in the Controls...

Page 15: ...tatus can be Bad Closed Open and Intermediate The status Intermediate isthephasebetween Open and Closed wherebothstatusinputsare0 The status Bad occurs when both status inputs of the object cart are 1...

Page 16: ...between open and close status change before intermittent status is reported by the function Max close and open pulse length Defines the maximum length of open and close commands If status has changed...

Page 17: ...connect object statuses directly to physical outputs in the Signal connections subsection Control Application control They can be connected to output relays as well as to user configurable LEDs A con...

Page 18: ...ike opening and closing time command type and request failures Data included in the register depend on the control function Youcan clear the operation register by choosing Clear registers Clear EVENTS...

Page 19: ...olfunctions module andselects the control function for furtherinspection Figure 3 4 15 Control functions submenu Each control function that has been activated is listed in the Control functions submen...

Page 20: ...plays the setting group that is currently in use and its settings other setting groups can be set in the Settings section While the function is activated and disabled in the Control Controls enabled s...

Page 21: ...egisters section you can find both Operation event register and General event register Operation event register stores the function s specific operation data There are twelve 12 registers and each of...

Page 22: ...onnect the stage s signals to physical outputs either to an output relay or an LED START or TRIP LEDs or one of the 16 user configurable LEDs If the stage is blocked internally DI or another signal yo...

Page 23: ...mark icon If you want to cancel the changes select the strike through circle to do so Only masked events are recorded to event history which can be accessed in the Events view in the user view sectio...

Page 24: ...lso a setting to determine the wanted activation and release delay 0 1800 s step 1 ms Digital input activation and release threshold follow the measured peak value The activation time of an input is 5...

Page 25: ...t descriptions allows you to configure the description text of each output All name changes affect the matrices as well as input output selection lists NOTE A NC signal goes to the default position NO...

Page 26: ...or non latched x Please note that a non latched output is deactivated immediately when the triggering signal is disabled while a latched signal stays active until the triggering signal deactivates and...

Page 27: ...g tool it is possible to set a text which is shown when input signal is ON and separate text for when the signal is OFF Figure 3 4 28 Logical signals subsection NP900 series units have three different...

Page 28: ...e matrix block functions and much more GOOSEinputs aremainly used for controlling purposes throughthe IEC 61850 There are 64 GOOSE inputs signal status bits and their status can be either 0 or 1 GOOSE...

Page 29: ...All devices can be configured through the Ethernet connection in the back panel with the SMART9 setting tool software Connecting to the SMART9 software requires knowing the IP address of your device c...

Page 30: ...c settings of RS 485 port in the back panel of the unit Bitrate displays the bitrate of the RS 485 serial communication interface 9600 bps as standard although can be changed to 19 200 bps or 38 400 b...

Page 31: ...Modbus TCP Ethernet communication protocol Modbus RTU Serial communication protocol IEC103 Serial communication protocol IEC101 104 The standards IEC 60870 5 101 and IEC 60870 5 104 are closely relat...

Page 32: ...enabled submenu By default all the control functions are disabled All activated functions can be viewed in the Monitor functions submenu see the section Monitor functions below for more information M...

Page 33: ...aring of all the latest or the oldestrecording Max amount of recordings displays the maximum number of recordings depends on the number of channels the sample rate and the length of the file Max lengt...

Page 34: ...abling Auto get recordings allows the device to automatically upload recordings to the designated FTP folder which in turn allows any FTP client to read the recordings from the IED s memory Rec digita...

Page 35: ...is locked with a password in an IED In order to activate the different user levels click the Lock button in the device s HMI and set the desired passwords for the different user levels NOTE Passwords...

Page 36: ...level of the different user levels is indicated by the number of stars The requiredaccessleveltochangeaparameterisindicatedwithastar symbolifsuchisrequired As a general rule the access levels are div...

Page 37: ...play has two different modes dynamic and fixed screen The fixed screen always lists 1 to 16 alarm texts on the display The dynamic screen starts with an empty display and fills up the list as alarms a...

Page 38: ...continuously lit LED A deactivated alarm text is displayed until the alarm has been cleared in the HMI This kind of alarm is displayed with a blinking LED in the Alarms display If the alarm signal s O...

Page 39: ...e Alarm Texts 1 and 2 The LEDs next to the texts are also lit up as long as the digital inputs are on When Digital Input 1 is deactivated the alarm text is still displayed but the LED will start blink...

Page 40: ...s needed it is possible to connect an external buzzer It is activated by one of the output relays of the IED The user can set up the buzzer control by connecting the Alarm Buzzer signal to an output C...

Page 41: ...OFF 772 12 ALARM1 4 Alarm 3 ON 773 12 ALARM1 5 Alarm 3 OFF 774 12 ALARM1 6 Alarm 4 ON 775 12 ALARM1 7 Alarm 4 OFF 776 12 ALARM1 8 Alarm 5 ON 777 12 ALARM1 9 Alarm 5 OFF 778 12 ALARM1 10 Alarm 6 ON 779...

Page 42: ...810 12 ALARM1 42 Alarm 22 ON 811 12 ALARM1 43 Alarm 22 OFF 812 12 ALARM1 44 Alarm 23 ON 813 12 ALARM1 45 Alarm 23 OFF 814 12 ALARM1 46 Alarm 24 ON 815 12 ALARM1 47 Alarm 24 OFF 816 12 ALARM1 48 Alarm...

Page 43: ...13 ALARM2 14 Alarm 40 ON 847 13 ALARM2 15 Alarm 40 OFF 848 13 ALARM2 16 Alarm 41 ON 849 13 ALARM2 17 Alarm 41 OFF 850 13 ALARM2 18 Alarm 42 ON 851 13 ALARM2 19 Alarm 42 OFF 852 13 ALARM2 20 Alarm 43 O...

Page 44: ...76 13 ALARM2 44 Alarm 55 ON 877 13 ALARM2 45 Alarm 55 OFF 878 13 ALARM2 46 Alarm 56 ON 879 13 ALARM2 47 Alarm 56 OFF 880 13 ALARM2 48 Alarm 57 ON 881 13 ALARM2 49 Alarm 57 OFF 882 13 ALARM2 50 Alarm 5...

Page 45: ...ogic inputs and connected digital inputs The user can also force any of the setting groups on when the Force SG change setting is enabled by giving the wanted quantity of setting groups as a number in...

Page 46: ...rol of the setting group selection Table 5 1 1 Settings of the setting group selection function Name Range Step Default Descri ption Active setting group SG1 Displays which setting group is active For...

Page 47: ...pulses or static signals If static signal control is applied no requests with a lower priority than SG1 and SG2 will be processed Setting group 4 0 Not active 1 Active 0 Not active The selection of Se...

Page 48: ...whether the Petersen coil is connected when the network is compensated or whether it is open when the network is unearthed Figure 5 1 3 Setting group control one wire connection from Petersen coil sta...

Page 49: ...nt is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 5 1 4 Setting group control two...

Page 50: ...pick up function see the image below Figure 5 1 5 Entirely application controlled setting group change with the cold load pick up function In these examples the cold load pick up function s output is...

Page 51: ...SG3 Enabled 4163 65 SGS 3 SG3 Disabled 4164 65 SGS 4 SG4 Enabled 4165 65 SGS 5 SG4 Disabled 4166 65 SGS 6 SG5 Enabled 4167 65 SGS 7 SG5 Disabled 4168 65 SGS 8 SG6 Enabled 4169 65 SGS 9 SG6 Disabled 41...

Page 52: ...4197 65 SGS 37 SG Request Fail Not configured SG OFF 4198 65 SGS 38 Force Request Fail Force ON 4199 65 SGS 39 Force Request Fail Force OFF 4200 65 SGS 40 SG Req Fail Lower priority Request ON 4201 6...

Page 53: ...ble Modbus IEC101 103 104 etc The function supports the modes Direct control and Select before execute while controlled remotely Automatic controlling can be done with functions like auto reclosing fu...

Page 54: ...emote switch Local controls cannot override the open and close commands while device is in Remote status The remote controls cannot override the open and close commands while device is in Local status...

Page 55: ...f the object Use Synchrochec k 0 Not in use 1 Synchrochec k in use 0 Not in use Selects whether the Synchrocheck condition is in use for the circuit breaker close command If In use is selected the inp...

Page 56: ...itored object If IEC 61850 is enabled GOOSE signals can be used for status indication SWx Objectx Close input Objectx Close Status In Digital input or other logical signal selected by the user A link...

Page 57: ...tx Breaker status setting If neither of the status inputs are active after this delay the status Intermediate is activated Maximum Close command pulse length 0 02 500 00 s 0 02 s 0 2 s Determines the...

Page 58: ...t e g a push button Objectx LOCAL Open control input Digital input or other logical signal selected by the user The local Open command from a physical digital input e g a push button Objectx REMOTE Cl...

Page 59: ...ch controllable object with Open and Close set separately Blocking and interlocking can be based on any of the following other object statuses a software function or a digital input The image below pr...

Page 60: ...ction instances 1 10 Event Number Event channel Event block name Event Code Description 2944 46 OBJ1 0 Object Intermediate 2945 46 OBJ1 1 Object Open 2946 46 OBJ1 2 Object Close 2947 46 OBJ1 3 Object...

Page 61: ...Command ON 3019 47 OBJ2 11 Open Command OFF 3020 47 OBJ2 12 Close Request ON 3021 47 OBJ2 13 Close Request OFF 3022 47 OBJ2 14 Close Command ON 3023 47 OBJ2 15 Close Command OFF 3024 47 OBJ2 16 Open B...

Page 62: ...d OFF 3090 48 OBJ3 18 Close Blocked ON 3091 48 OBJ3 19 Close Blocked OFF 3092 48 OBJ3 20 Object Ready 3093 48 OBJ3 21 Object Not Ready 3094 48 OBJ3 22 Sync Ok 3095 48 OBJ3 23 Sync Not Ok 3096 48 OBJ3...

Page 63: ...l 3162 49 OBJ4 26 Final trip ON 3163 49 OBJ4 27 Final trip OFF 3200 50 OBJ5 0 Object Intermediate 3201 50 OBJ5 1 Object Open 3202 50 OBJ5 2 Object Close 3203 50 OBJ5 3 Object Bad 3204 50 OBJ5 4 WD Int...

Page 64: ...07 150 OBJ6 7 WD Bad 9608 150 OBJ6 8 Open Request ON 9609 150 OBJ6 9 Open Request OFF 9610 150 OBJ6 10 Open Command ON 9611 150 OBJ6 11 Open Command OFF 9612 150 OBJ6 12 Close Request ON 9613 150 OBJ6...

Page 65: ...ose Command ON 9679 151 OBJ7 15 Close Command OFF 9680 151 OBJ7 16 Open Blocked ON 9681 151 OBJ7 17 Open Blocked OFF 9682 151 OBJ7 18 Close Blocked ON 9683 151 OBJ7 19 Close Blocked OFF 9684 151 OBJ7...

Page 66: ...0 152 OBJ8 22 Sync Ok 9751 152 OBJ8 23 Sync Not Ok 9752 152 OBJ8 24 Open Command Fail 9753 152 OBJ8 25 Close Command Fail 9754 152 OBJ8 26 Final trip ON 9755 152 OBJ8 27 Final trip OFF 9792 153 OBJ9 0...

Page 67: ...ose 9859 154 OBJ10 3 Object Bad 9860 154 OBJ10 4 WD Intermediate 9861 154 OBJ10 5 WD Out 9862 154 OBJ10 6 WD In 9863 154 OBJ10 7 WD Bad 9864 154 OBJ10 8 Open Request ON 9865 154 OBJ10 9 Open Request O...

Page 68: ...on takes care of the status monitoring of disconnectors The function s sole purpose is indication and does not therefore have any control functionality To control circuit breakers and or disconnectors...

Page 69: ...r logical signal selected by the user SWx A link to a physical digital input The monitored indicator s OPEN status 1 refers to the active Open state of the monitored indicator If IEC 61850 is enabled...

Page 70: ...rent does not change as it travels from a transmitter to a receiver It is also much more simple and cost effective The benefits of 4 20 mA loops the dominant standard in many industries the simplest o...

Page 71: ...the channel settings are hidden Magnitude selection for mA output channel 0 Currents 1 Voltages 2 Powers 3 Impedance and admittance 4 Other 0 Currents Defines the measurement category that is used fo...

Page 72: ...s Name Range Step Description mA in Channel 1 0 0000 24 0000 mA 0 0001 mA Displays the measured mA value of the selected input channel mA in Channel 2 Input magnitude of the mA output channel 10 7 10...

Page 73: ...er see the image below calculates the average of received mA signals according to the set time constant This is why rapid changes and disturbances such as fast spikes are smothered The Nyquist rate st...

Page 74: ...rement update cycle If the user wants a fast operation this setting should be fairly low Scaled value handling 0 Floating point 1 Integer out Floor 2 Integer Ceiling 3 Integer Nearest 0 Floating point...

Page 75: ...digital inputs or logic signals it can only be controlled locally mimic or remotely RTU Settings These settings can be accessed at Control Device I O Programmable control switch Table 6 3 17 Settings...

Page 76: ...rameter at 0 0 0 0 means that the server is not in use Table 7 1 1 2 Client settings Name Range Description IP address 0 0 0 0 255 255 255 255 Defines the address of the NTP client NOTE This address m...

Page 77: ...T9 software Tools Communication Modbusmap Please note that holding registers start from 1 Some masters might begin numbering holding register from 0 instead of 1 this will cause an offset of 1 between...

Page 78: ...n that is dedicated to communicating with serial Modbus RTU slaves such as RTD input modules Up to three 3 Modbus RTU slaves can be connected to thesamebuspolledbythe ModbusI O implementation Theseare...

Page 79: ...ization The device s current IEC 61850 setup can be viewed with the IEC61850 tool Tools IEC 61850 By browsing the 61850 tree one can see the full list of available logical nodes in the ICE implementat...

Page 80: ...ain configurations dialog window is opened by pressing the sixth button Configurations in the main toolbar The most important parameters here are the IED name and the IP settings Additionally if the i...

Page 81: ...editing dialog shows all currently configured entries of the data set An entry can be removed from the data set by clicking the red button located at the end of the entry s row New entries can be add...

Page 82: ...00 0 kVar 0 1 kVar 2 kVar Determines the data reporting deadband settings forthis measurement Apparent power deadband 0 1 1000 0 kVA 0 1 kVA 2 kVA Determines the data reporting deadband settings forth...

Page 83: ...the GOOSE input in question Application ID AppID 0 0 0 3FFF 0 1 0 0 Defines the application ID that will be matched with the publisher s GOOSE control block Configuration revision ConfRev 1 2 32 1 1 1...

Page 84: ...out supervision have to be of good quality or else the quality signal activates 7 1 6 IEC 103 IEC 103 is shortened form of the international standard IEC 60870 5 103 The NP900 series units are able to...

Page 85: ...disables the DNP3 TCP communication protocol when the Ethernet port is used for DNP3 If a serial port is used the DNP3 protocol can be enabled from Communication DNP3 IP port 0 65 535 1 20 000 Defines...

Page 86: ...nal change Group 3 variation DBI 0 Var1 1 Var2 0 Var 1 Selects the variation of the double point signal Group 4 variation DBI change 0 Var1 1 Var2 1 Var 2 Selects the variation of the double point sig...

Page 87: ...ing deadband settings forthis measurement Apparent power deadband 0 1 1000 0 kVA 0 1 kVA 2 kVA Determines the data reporting deadband settings forthis measurement Power factor deadband 0 01 0 99 0 01...

Page 88: ...ze of the common address of ASDU Link layer address 0 65 534 1 1 Defines the address for the link layer Link layer address size 1 2 1 2 Defines the address size of the link layer Information object ad...

Page 89: ...ies without authorization Instruction Manual NPS914 Alarm and Indication IED Frequency Current Residual current Voltage Residual voltage Angle The range is the same for all of the scaling coefficients...

Page 90: ...deadband settings forthis measurement Residual current deadband 0 01 50 00 A 0 01 A 0 2 A Determines the data reporting deadband settings forthis measurement Voltage deadband 0 01 5000 00 V 0 01 V 20...

Page 91: ...lt registerrecording The user can choose between non directional overcurrent directionalovercurrent non directionalearthfault directional earth fault and fault locatorfunctions Select record trigger 0...

Page 92: ...t and zero sequence current I0CalcMag Residual current calculated from phase currents IL1Ang IL2Ang IL3Ang I01Ang I02Ang I0CalcAng I1Ang I2Ang Angles of each measured current Voltages UL1Mag UL2Mag UL...

Page 93: ...emperature T thermal T Transformer thermal temperature RTD meas 1 16 RTD measurement channels 1 16 Ext RTD meas 1 8 External RTD measurement channels 1 8 ADAM module Settings Table 7 3 19 Settings Nam...

Page 94: ...ty of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED 8 Connections and application examples 8 1 Connections...

Page 95: ...s document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 8 1 2 NPS914 variant wit...

Page 96: ...B Page 96 This document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 8 1 3 NPS91...

Page 97: ...rentapplication requirements In non standard configurations Slots A B C D E and F accept all available add on modules such as digital I O modules or a special module The only difference between the sl...

Page 98: ...finds and assigns DI1 DI2 DI3 OUT1 OUT2 OUT3 OUT4 and OUT5 2 Scan Scans Slot A and moves to the next slot if Slot A is empty If the scan finds an 8DI module that is a module with eight digital inputs...

Page 99: ...signations have been reserved by modules in previous slots and numbers the new ones accordingly Thus far this document hasonly explained the installation of I O add on cards to the option module slots...

Page 100: ...vethefollowingdesignations Pin1 DATA Pin 2 DATA Pin 3 GND Pins 4 5 Terminator resistor enabled by shorting Model with 3 digital inputs Model with 2 digital inputs X 1 Digital input 1 nominal threshold...

Page 101: ...le are A 85 265 VAC DC and B 18 75 DC For further details please refer to the Auxiliary voltage chapter in the Technical data section of this document Digital input settings The settings described in...

Page 102: ...ht 8 galvanically isolated digital inputs This module can be ordered directly to be installed into the device in the factory Thepropertiesoftheinputsinthismodulearethe same as those of the inputs in t...

Page 103: ...larity themeasuredvoltagebelowthis setting deactivates the input When NC is the selected polarity the measured voltage below this setting activates the input DIx Activation delay 0 000 1800 000 s 0 00...

Page 104: ...ommunicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED The diagram below depicts the digital input states when the input channels are energized and de en...

Page 105: ...he DO5 module is an add on module with five 5 digital outputs This module can be ordered directly to be installed into the device in the factory The properties of the outputs in this module are the sa...

Page 106: ...nels Each input supports 2 wire 3 wire and 4 wire RTD sensors as well as thermocouple TC sensors The sensor type can be selected with software for two groups four channels each The supported sensor ty...

Page 107: ...This document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 9 5 8 Different sens...

Page 108: ...0 nm Compatible with 50 125 m 62 5 125 m 100 140 m and 200 m Plastic Clad Silica PCS fiber Compatible with ST connectors COM F Pin 1 24 V input Optional external auxiliary voltage for serial fiber COM...

Page 109: ...or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Connector Name Description COM F Pin 12 The option card includes two serial communication int...

Page 110: ...tion module optional Figure 9 7 10 LC 100 Mbps Ethernet module connectors Connector Description COM C Communication port C LC fiber connector 62 5 125 m or 50 125 m multimode glass Wavelength 1300 nm...

Page 111: ...nm nominal 1310 nm Receiver wavelength 1100 1600 nm 100BASE FX Up to 2 km This option cards supports redundant ring configuration and multidrop configurations Redundant communication can be implemente...

Page 112: ...he property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 9 8 12 Example of a ring configuration...

Page 113: ...T and 100BASE TX This option card supports redundant ring configuration and multidrop configurations Redundant communication can be implemented by Ethernet switches that support Rapid Spanning Tree Pr...

Page 114: ...he property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 9 9 15 Example of a ring configuration...

Page 115: ...cutouts The desired installation type is defined in the order code When installing to a rack the device takes a quarter of the rack s width meaning that a total of four devices can be installed to the...

Page 116: ...This document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IED Figure 9 10 19 Panel cutout...

Page 117: ...y voltage 85 265 V AC DC Power consumption 7 W 15 W Maximum permitted interrupt time 60 ms with 110 VDC DC ripple 15 Terminal block connection Terminal block Phoenix Contact MSTB 2 5 5 ST 5 08 Solid o...

Page 118: ...MB System integration Cannot be used for system protocols only for local programming Table 10 1 1 2 4 Rear panel system communication port A Port Port media Copper Ethernet RJ 45 Number of ports 1 Fe...

Page 119: ...ms Settings Pick up delay Software settable 0 1800 s Polarity Software settable Normally On Normally Off Current drain 2 mA Terminal block connection Terminal block Phoenix Contact MSTB 2 5 5 ST 5 08...

Page 120: ...l outputs Change Over Rated values Rated auxiliary voltage 265 V AC DC Continuous carry 5 A Make and carry 0 5 s Make and carry 3 s 30 A 15 A Breaking capacity DC L R 40 ms at 48 VDC at 110VDC at 220V...

Page 121: ...V Pick up delay Software settable 0 1800 s Drop off delay Software settable 0 1800 s Polarity Software settable Normally On Normally Off Terminal block connection Terminal block Phoenix Contact MSTB 2...

Page 122: ...ule Table 10 1 2 4 12 Technical data for the RS 232 serial fiber communication module Ports RS 232 Serial fiber GG PP GP PG Serial port wavelength 660 nm Cable type 1 mm plastic fiber 10 1 2 5 Double...

Page 123: ...e overrule of local controls either from the setting tool HMI or SCADA Operation time Reaction time 5 ms from receiving the control signal 10 2 1 2 Object control and monitoring Table 10 2 1 2 16 Tech...

Page 124: ...l fast transients EFT EN 60255 26 IEC 61000 4 4 Power supply input 4 kV 5 50 ns 5 kHz Other inputs and outputs 4 kV 5 50 ns 5 kHz Surge EN 60255 26 IEC 61000 4 5 Between wires 2 kV 1 2 50 s Between wi...

Page 125: ...d test EN 60255 1 IEC 60068 2 1 Storage 40 C 16 h Operational 20 C 16 h Table 10 3 21 Environmental conditions IP classes Casing protection class IP54 front IP21 rear Temperature ranges Ambient servic...

Page 126: ...ference A938 Index B Page 126 This document is the property of ICE SAS It can not be reproduced or communicated to third parties without authorization Instruction Manual NPS914 Alarm and Indication IE...

Reviews: