Instruction Manual – NPS914 Alarm and Indication IED
Name
Range
Step
Default
Description
Remote
SG
change
0: None
1: SG1
2: SG2
3: SG3
4: SG4
5: SG5
6: SG6
7: SG7
8: SG8
-
0: None
This parameter can be controlled through SCADA to change the setting group
remotely. Please note that if a higher priority setting group is being controlled by a
signal, a lower priority setting group cannot be activated with this parameter.
Table. 5.1. - 2. Signals of the setting group selection function.
Name
Range
Step
Default
Descripti
on
Setting
group 1
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 1 ("SG1"). Has the highest priority input in setting
group control. Can be controlled with pulses or static signals. If static signal control
is applied, no other SG requests will be processed.
Setting
group 2
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 2 ("SG2"). Has the second highest priority input in
setting group control. Can be controlled with pulses or static signals. If static signal
control is applied, no requests with a lower priority than SG1 will be processed.
Setting
group 3
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 3 ("SG3"). Has the third highest priority input in
setting group control. Can be controlled with pulses or static signals. If static
signal
control is applied, no requests with a lower priority than SG1 and SG2 will be
processed.
Setting
group 4
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 4 ("SG4"). Has the fourth highest priority input in
setting group control. Can be controlled with pulses or static signals. If static
signal
control is applied, no requests with a lower priority than SG1, SG2 and SG3 will be
processed.
Setting
group 5
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 5 ("SG5"). Has the fourth lowest priority input in
setting group control. Can be controlled with pulses or static signals. If static
signal
control is applied, SG6, SG7 and SG8 requests will not be processed.
Setting
group 6
0:Not
active
1:Active
-
0:Not
activ
e
The selection of Setting group 6 ("SG6"). Has the third lowest priority input in
setting group control. Can be controlled with pulses or static signals. If static signal
control is applied, SG7 and SG8 requests will not be processed.
Setting
group 7
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 7 ("SG7"). Has the second lowest priority input in
setting group control. Can be controlled with pulses or static signals. If static signal
control is applied, only SG8 requests will not be processed.
Setting
group 8
0: Not
active
1:
Active
-
0: Not
active
The selection of Setting group 8 ("SG8"). Has the lowest priority input in setting
group control. Can be controlled with pulses or static signals. If static signal control
is applied, all other SG requests will be processed regardless of the signal status
of this setting group.