Instruction Manual – NPS914 Alarm and Indication IED
Table. 6. - 5. Control settings (DI and Application).
Signal
Range
Description
Access level for MIMIC
control
0: User
1: Operator
2: Configurator
3: Super user
Defines what level of access is required for MIMIC control.
The default is the "Configurator" level.
Objectx LOCAL
Close control input
Digital input or other logical
signal selected by the user
The local Close command from a physical digital input (e.g. a
push button).
Objectx LOCAL
Open control
input
Digital input or other logical
signal selected by the user
The local Open command from a physical digital input (e.g. a
push button).
Objectx
REMOTE Close control
input
Digital input or other logical
signal selected by the user
The remote Close command from a physical digital input (e.g.
RTU).
Objectx REMOTE
Open control
input
Digital input or other logical
signal selected by the user
The remote Open command from a physical digital input (e.g.
RTU).
Objectx
Application Close
Digital input or other logical
signal selected by the user
The Close command from the application. Can be any
logical signal.
Objectx
Application Open
Digital input or other logical
signal selected by the user
The Close command from the application. Can be any
logical signal.