background image

MODBUS I/O module
16 Isolated
Digital Inputs
mod.

IO-MB/DI-16LV

ASCON spa

20021 Baranzate (Italy)
Fax +39 02 350 4243
www.ascon.it
[email protected]

mod.

IO-MB/DI-16LV

E

M . U . I O - M B / D I - 1 6 LV - 3 / 0 9 . 0 2

C o d .

J 3 0 - 6 5 8 - 1 A D I - 1 6 LV   E

ISO9001 Certified

Functional Block Diagram

16 optoisolated digital inputs with
special functions

- Latched inputs

.

Characteristics

Local Mode

Local Value

Remote

Transmit

Input

DI 1...16

Module
config.

Latched
DI 1...16

Technical data

A

PPLICABLE STANDARDS

The DI-16LV module is suited for the Modbus-IDA Organization protocol [1] and imple-
ments a subset of it, as explained in the text. MODBUS is a registered trademark of
Schneider Automation Inc.

A

W

ARNING

The product described in this manual should only be installed, operated and maintained by
qualified application programmers and software engineers who are familiar with automation
safety concepts and applicable national standards.

Number of channels

16

Polarity (EN 61131-2 type 2)

Sink

UL (state 0)

-3...+11/5 Vdc

UT (transition)

5...11 Vdc

UH (state 1)

11... 30 Vdc

Input impedance

5 k

ON/OFF delay

5 ms

Max. monostable time

65 s

General

Environment

Operating

Storage

Temperature

-10...+65°C

-40...+85°C

5...95% non condensing

5...95% non condensing

Relative

Appropriate measures must

For a short period, slight

Humidity

be taken against 

condensation may appear 

humidity >85%

on the housing

Mounting

Vertical, free air

Protection

IP20

Vibrations (3 axes) 10...57Hz 0.0375mm, 57...150Hz 0.5g
Shock (3 axes)

15g, 11ms half sine

3 way isolation

Ch. to ch.: no isolation; ch. to logic: 800 Vp

(see last page)

serial bus to logic: 800 Vp; power supply to logic: 2.5 kVp

Power supply

24 Vdc; –15...+25%

Consuption: 3 W

Overvoltage protection 40 Vdc
Dimensions

L: 76; H: 110; W: 65;

Weight: 220g

Safety regulations

Isolation class II

(50 Vrms), Installation cathegory II

EN61010-1

Pollution degree 2

CE marking

EN61131-2

Function Codes used by the module

The function codes provided for all the modules are a subset of the “Public Function
Codes”, validated by the Modbus-IDA Organization.

Function 01 and Function 02 can be used to read both digital output and digital input.
Function 03 and Function 04 can be used to read both output and input registers.

Functions

(hex)

Physical Digital Inputs

Read Inputs status

02

02

Bit

Internal Bits Or

Read Coil status

01

01

access

Physical Digital

Write Single Coil

05

05

Data

output

Write Multiple Coils

15

0F

access

Physical Input Registers

Read Input Register

04

04

Word

Internal Registers

Read Holding Registers

03

03

access

Or Physical Output

Write Single Register

06

06

Registers

Write Multiple Registers

16

10

Diagnostics

Read Exception status

07

07

Diagnostics

08

08

Diagnostics

MODBUS Exception Responses:

Code Name

Meaning

01

ILLEGAL FUNCTION

The function code received in the query is not an
allowable action for the server (or slave)

02

ILLEGAL DATA

The data address received in the query is not an

ADDRESS

allowable address for the server (or slave).

03

ILLEGAL DATA

A value contained in the query data field is not an 

VALUE

allowable value for server (or slave)

07

NEGATIVE 

The server (or slave) is in the wrong state to process

ACKNOWLEDGE a 

request of this type or an attempt to write to a read

- NAK

only address has been made

Code 07 has not been provided by Modbus.org Protocol. Use it for ASCON products com-
patibility only.

Function Code 07:

Read Exception Status:

Function Code 08:

Diagnostics

The only supported sub code is 0 – Return Query Data

Digital Input writing attempted (1)
Dummy Data Field (0 fill) (1)
Output Data Valid (1)

Local Value state (1)

Invalid Input Data (1)

bit

7

6

5

4

3

2

1

0

status

0

0

0

X

X

X

X

X

User manual

Contents

-

Characteristics

- Functional Block Diagram
-

Function Codes used by the module

-

Diagnostics

-

MODBUS Address Map organisation

-

Hardware Setup

- Common 

parameters

- Module 

parameters

- Parameters Store/Restore
- Three way isolation diagram
- MODBUS Map summary

DI-16LV-uso-e  3-02-2009  10:43  Pagina 1