ELEVATION SERIES CIM CUBERS
REMOTE CONDENSER GUIDELINES
6
Equivalent Run Calculation Examples
Formula for maximum equivalent run:
(RISE X 1.7) + (DROP X 6.6) + HORIZONTAL RUN = CALCULATED LINE RUN
NOT TO EXCEED 100 CALCULATED FEET
Rise:
(35 ft. x 1.7) + (40 ft.) = 99.5 calculated feet line run
Drop:
(10 ft. x 6.6) + (34 ft.) = 100 calculated feet line run
40 ft. horizontal
35 ft. rise
34 ft. horizontal
10 ft. drop