ELEVATION SERIES CIM CUBERS
SEQUENCE OF OPERATIONS
21
CONTROL BOARD - HARVEST
After the Purge Valve and Water Pump de‐energize, the Water Inlet Valve will remain open for 20 sec‐
onds, partially filling the SUMP in preparation for the next Freeze Cycle (R2, R3, and R4, are illuminated
on Air and Water Cooled units, R1 is also energized on Remotes.) The Low Float Switch will go off as the
water level rises.
The Hot Gas Valve and Harvest Assist will remain energized for the remainder of the Harvest Cycle.
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage
Components
R1
R2
R3
R4
R5
R6