Appendix B – Guide Specifications
Appendix B – Guide Specifications
Ice Storage Air Conditioning (ISAC) System
Cooling Capacity
:
Nominal 30 ton-hrs, 5 ton capacity
Duty
:
exterior installation
Part 1 – General
1.01
SYSTEM DESCRIPTION
A.
Outdoor rated ISAC system suitable for pad mounted on-the-ground or rooftop installation. The
ISAC replaces a standard compressor / condenser in order to disassociate system power
consumption from the cooling load profile. The unit will provide cooling to building(s) by
melting stored ice. Ice is made during off-peak periods by an integrated condensing unit, as
determined by an internal controller. Unit shall consist of an ice storage tank with means of heat
extraction and rejection (heat exchanger), R-410A refrigerant, refrigerant management system,
refrigerant pump, and a standard condensing unit.
1.02
QUALITY ASSURANCE
A.
ISAC system shall be rated in accordance with established procedures for testing the Ice Make
and Ice Cooling performance accepted and approved by the California Energy Commission
B.
ISAC system constructed shall comply with ANSI/ASHRAE 15 safety code latest revision and
comply with NEC
C.
ISAC system shall be constructed in accordance with UL 1995 standard
D.
ISAC system storage tank shall be capable of withstanding 500-hour salt spray exposure per
ASTM B117
E.
Ice storage heat exchange coils shall be leak tested at 150 psig and pressure tested at 275 psig.
1.03
DELIVERY STORAGE AND HANDLING
ISAC system shall be stored and handled according to the manufacturers’ recommendation.
1.04
WARRANTY
Limited warranty for parts and labor per manufacturers’ policy with the following period
limitations:
A.
Compressor: 5 years from warranty commencement date
B.
Condensing Unit Heat Exchanger: 5 years from warranty commencement date
C.
Ice Storage Tank & Unit Heat Exchanger : 5 years from warranty commencement date
Part 2 – Products
2.01 EQUIPMENT
A.
General:
Factory-assembled ISAC. Contained within the unit enclosure shall be all factory wiring, piping,
controls, and features required prior to field startup.
B.
Ice Storage Tank
1.
Storage tank shall be constructed of durable rotomolded polyethylene with a 3/8 inch
wall thickness.
2.
Ice Storage Tank shall not require water service after initial install.
C.
Integrated Ice Making Unit
The ISAC shall include an integrated Ice Making unit.
D.
Refrigerant Management System
Ice Bear
®
30 Unit Application Guide