Installation Considerations
Mounting
The Ice Bear
®
30 unit weights are as follows:
Weight (without water)
1,550 lb
Weight (filled)
5,550 lb
Load distribution (filled)
156 lb per ft
2
204 lb per linear ft
Ground Mounting
Provide leveling in compliance with local codes for clearance, easements, and soil compaction
restrictions. The Ice Bear unit must be level to within 1/8" in all directions.
Concrete Pad
•
A concrete pad or other approved surface may be used, as designed and reviewed by a licensed
structural engineer.
•
Refer back to
Minimum Clearances
.
•
See Figure 25 for minimum recommended pad dimensions.
•
Figure 26 provides a sample drawing of a precast concrete pad.
NOTE:
Local codes/regulations may prevail.
Concrete
Pad
Ice Bear
Unit Base
Figure 25 – Minimum Recommended Concrete Pad Dimensions
28 Ice
Bear
®
30 Unit Application Guide