Engineering
Data
Engineering Data
Ice Bear
®
30 Unit Ambient Temperature Operating Ranges
Ice Make
•
Performance tested Ice Make temperature range: 55 °F to 95 °F
•
Enabled Ice Make temperature range: 15 °F to 115 °F
•
Ice Make is automatically disabled below 15 °F or higher than 115 °F.
Ice Cooling
•
Cooling performance is independent of ambient conditions above 15 °F.
•
Ice Cooling is automatically disabled when ambient is below 15 °F.
Ice Bear
®
30 Unit ETL Certified Performance Data
Table 5. Ice Make Capacity & Power at Ambient Temperature
Outdoor Temperature (°F)
Ti
me (hrs
)
55° 65° 75° 85° 95°
Capacity Energy Capacity Energy Capacity Energy Capacity Energy Capacity Energy
Stored Consumed Stored Consumed
Stored Consumed Stored Consumed Stored Consumed
(T-hrs) (kW-hr) (T-hrs) (kW-hr) (T-hrs) (kW-hr) (T-hrs) (kW-hr) (T-hrs) (kW-hr)
1
3.61 2.88 3.49 3.19 3.33 3.53 3.08 3.96 2.80 4.40
2
7.15 5.72 6.76 6.33 6.47 7.00 6.00 7.84 5.46 8.70
3
10.61 8.54 10.01 9.46 9.56 10.47 8.88 11.70 8.07 12.99
4
14.03 11.35 13.22 12.59 12.62 13.94 11.71 15.55 10.66 17.27
5 17.4 14.16 16.41 15.71 15.64 17.41 14.52 19.40 13.23 21.55
6
20.77 16.97 19.59 18.83 18.66 20.87 17.32 23.24 15.79 25.83
7
24.12 19.77 22.74 21.94 21.66 24.32 20.10 27.08 18.35 30.10
8
27.46 22.57 25.89 25.04 24.64 27.78 22.88 30.92 20.89 34.37
9
30.75 25.36 29.01 28.13 27.60 31.24 25.63 34.76 23.43 38.63
10
31.57 26.06 31.57 30.71 30.52 34.70 28.38 38.59 25.95 42.89
11
31.57
35.95
31.09
42.42
28.46
47.15
12
31.57
43.11
30.94
51.40
13
31.57
52.50
Actual Make Time (hrs)
9.24
9.84
10.36
11.17
12.25
Typical
Demand
(kW)
2.82 3.12 3.47 3.86 4.28
Ice Bear
®
30 Unit Application Guide