Product Data and Specifications
Product Data and Specifications
Table 1. Ice Bear 30 Unit Cooling Performance
Maximum instantaneous cooling capacity
5 tons
Total storage module capacity
30 ton-hours
Maximum on-peak electrical demand (at maximum
application parameters, excluding crankcase heater)
350 watts
Nominal on-peak electrical demand (typical installation)
300 watts
Ice Make/recharge time
(from fully melted tank of ice)
11.5 hours at 75 °F
outdoor ambient temp.
Table 2. Ice Bear 30 Unit Physical Properties
Dimensions (W x D x H)
100-1/2” x 61” x 49”
Weight (without water)
1,550 lb.
Weight (filled)
5,550 lb.
Load distribution (filled)
204 lb/linear ft
(156 lb. per ft
2
)
Water volume
475 gallons
Refrigerant charge, tank (Ice Cooling)
35 lb R-410A (factory)
Refrigerant charge, compressor (Ice Make)
11 lb 8 oz R-410A (factory)
Table 3. Ice Bear 30 Unit Electrical Properties
Model System
Type
Minimum
Circuit
Ampacity
(MCA)
Maximum
Fuse
IB30A-521
208/230V, 1
φ
41.7 50
IB30A-523
208/230V, 3
φ
27.2 30
IB30A-543
460V, 3
φ
13.3 20
Table 4. Ice Bear 30 Unit Sound Ratings
Outdoor Sound Power Level dB – (ref. 10
-12
W)
Overall
dBA
Octave Center Frequency
63 125 250 500 1000 2000 4000 8000
IB30A
80
79.8 84.4 83.3 74.3 72.7 71.3 64.9 56.7
Notes:
1.
Above ratings are values derived during Ice Making mode.
2.
Compressor/condenser vibration isolation provided by OEM per equipment manufacturers’ standard specifications.
3.
Outdoor sound data measured by Intertek in accordance with ARI Standard 370.
4.
Ice Make ambient conditions for this test were 69 °F and 55% RH.
5.
This test is not part of the ARI Certification.
6.
Uncertified sound testing during Ice Cooling mode resulted in a level of 68 dBA.
Ice Bear
®
30 Unit Application Guide