Installation Considerations
Minimum Requirements for Connection of CoolData
®
Controller
Wiring
The below items are the minimum requirements for basic common installations. Depending on the scope
of a given installation, additional wiring may be required. Consult plans and engineering drawings to
determine actual requirements. Contact Ice Energy Product Services (call (877) 542-3232) or email
[email protected]) if you have questions.
•
Conform to engineering layout drawings showing locations of wiring and thermostat.
•
Document deviations in the Startup & Verification Report (F018).
•
Use one #18AWG insulated 8 conductor cable between Ice Bear unit and each base unit (e.g., air
handler, packaged unit, ductless Ice-Coil) for control only.
•
Use one #18AWG insulated (minimum 4 conductor) cable per Current Transducer and one
unshielded (UTP) CAT5e cable between each monitored base unit and the Ice Bear unit for
monitoring only.
•
If an alternate data service connection is required, use one CAT5e cable between the Ice Bear unit
and the alternate data service (Internet) location.
32 Ice
Bear
®
30 Unit Application Guide