Use
the
test
and
alarm
reset
button
to
start
the
self-test.
The
load-level
indicators
show
the
percentage
of
uninterruptible
power
supply
(UPS)
5125
capacity
that
the
SAN
Volume
Controller
is
using.
The
site
wiring
fault
indicator
on
the
uninterruptible
power
supply
(UPS)
5125
shows
that
either
a
ground
wire
connection
does
not
exist
or
the
live
and
neutral
wires
are
reversed
in
the
input
power
connection.
The
battery
service
indicator
shows
that
the
charge
in
the
battery
has
become
low
while
the
uninterruptible
power
supply
(UPS)
5125
is
in
battery
mode.
The
battery
mode
indicator
shows
that
the
uninterruptible
power
supply
(UPS)
5125
is
operating
on
batteries.
The
general
alarm
indicator
on
the
uninterruptible
power
supply
(UPS)
5125
turns
on
when
a
power
or
temperature
problem
occurs.
Mode
indicator
The
mode
indicator
provides
status
information
on
the
uninterruptible
power
supply
(UPS)
5125.
The
mode
indicator
is
located
on
the
front
panel
of
the
UPS
5125.
When
the
mode
indicator
is
steady
green,
the
UPS
5125
is
in
normal
mode.
The
UPS
5125
checks
and
charges
its
battery
as
necessary.
When
the
mode
indicator
is
flashing
green,
the
UPS
5125
is
in
standby
mode.
Standby
mode
means
that
the
UPS
5125
is
turned
off,
but
is
still
connected
to
the
main
power
source.
No
power
is
available
from
the
UPS
5125
output
sockets
but
the
UPS
5125
monitors
and
charges
its
battery
as
necessary.
When
the
mode
indicator
is
steady
red,
the
UPS
5125
is
in
bypass
mode
because
of
one
of
the
following
conditions:
v
The
UPS
5125
has
overheated
v
The
UPS
5125
has
an
overload
condition
of
103%
through
110%
for
30
seconds
v
The
UPS
5125
detects
a
fault
in
the
battery
or
in
the
UPS
5125
electronics
assembly
When
the
mode
indicator
is
flashing
red
and
the
alarm
is
sounding,
the
voltage
range
setting
might
not
be
correct.
When
a
SAN
Volume
Controller
is
connected
to
the
UPS
5125,
the
SAN
Volume
Controller
automatically
adjusts
the
voltage
range
setting.
Take
no
action
for
this
alarm
condition
unless
it
persists
for
more
than
five
minutes
after
a
SAN
Volume
Controller
has
been
connected
to
this
UPS
5125
and
powered
on.
On
button
The
on
button
turns
on
the
main
power
to
the
uninterruptible
power
supply
(UPS)
5125.
Chapter
2.
Overview
of
the
uninterruptible
power
supply
23
Summary of Contents for TotalStorage SAN Volume Controller
Page 1: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 2 1 0 SC26 7541 04...
Page 2: ......
Page 3: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 2 1 0 SC26 7541 04...
Page 8: ...vi IBM TotalStorage SAN Volume Controller Installation Guide...
Page 10: ...viii IBM TotalStorage SAN Volume Controller Installation Guide...
Page 11: ...Tables 1 Uninterruptible power supply support guidelines 17 Copyright IBM Corp 2003 2005 ix...
Page 12: ...x IBM TotalStorage SAN Volume Controller Installation Guide...
Page 30: ...xxviii IBM TotalStorage SAN Volume Controller Installation Guide...
Page 44: ...14 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 62: ...32 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 102: ...72 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 108: ...78 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 114: ...84 IBM TotalStorage SAN Volume Controller Installation Guide...
Page 121: ......
Page 122: ...Part Number 64P8289 Printed in USA SC26 7541 04 1P P N 64P8289...
Page 123: ...Spine information IBM TotalStorage SAN Volume Controller Installation Guide Version 2 1 0...