Table 21. ESS power cable connectors
Power cable
Feature Code
Power cable Description (See
Notes 1 and 3.)
In-line Connector
(See Note 2.)
Receptacle (See
Note 2.)
9801, 9986
1-phase, 50/60 Hz 50 A (See
Notes 4 and 10.)
9C53U0 (See Note
8.)
9R53U0W (See
Note 9, 10, and
12.)
9802
1-phase, 50 Hz (See Notes 4
and 10.)
No connector
Hard wire (See
note 10 and 12.)
9803
1-phase, 50/60 Hz, 60 A (See
Note 4.)
Not used
360R6W (See
Note 6, 10, and
12.)
9851, 9987
3-phase, 50/60 Hz, 50 A (See
Notes 5 and 10.)
9C54U0 (See Note
8.)
9R54U0W (See
Note 9, 11, and
13.)
9988, 9854
3-phase, 50/60 Hz, 60 A (See
Notes 5 and 10.)
7428-78 (See Note
7.)
7324-78 (See note
11 and 13.)
9852
3-phase, 50 Hz, (See Notes 5
and 11.)
No connector
Hard wire (See
note 11 and 13.)
9853
3-phase, 50/60 Hz, 60 A (See
Note 5.)
Not used
460R9W (See
Note 6, 11, and
13.)
Notes:
1. All power cables are rated at 600 V ac except power cables for Japan, which are 250
V ac. Single-phase power cables have 2 poles and 3 wires. Three-phase power cables
have 3 poles and 4 wires.
2. Connector and receptacle types indicated are Russell Stoll except types for Japan,
which can use any manufacturer.
3. All power cables are 4.7 m (14 ft) long except Chicago, which is 2 m (6 ft) long.
4. Not available on the Model E20 or F20 or the expansion enclosure.
5. Not available on the Model E10 or F10.
6. Install IEC309 receptacle in a metal-backed box with the green wire ground-connected
to the grounding lug within the box. Ensure continuity between the box and the metallic
shielding of the liquid-tight conduit.
7. The 7428-78 in-line connector must have the appropriate JPA adapter included in the
assembly to ensure continuity between the connector housing and the metallic
shielding of the liquid-tight conduit.
8. IBM recommends that you attach these in-line connectors to a liquid-tight,
metallic-shielded conduit, using adapter C75 for 1.89 cm (3/4-in.) conduit, or using C10
for 2.54 cm (1-in.) conduit.
9. These receptacles require back box 3711A.
10. For low-voltage, single phase installations (200 V to 240 V), IBM recommends a
minimum rated circuit breaker of 40 amperes, and not to exceed the wire rating of the
facility.
11. For low-voltage, three phase installation (200 V to 240 V), IBM recommends a
minimum rated circuit breaker of 25 amperes, and not to exceed the wire rating of the
facility.
12. For high-voltage, single phase installations (380 V to 415 V), IBM recommends a
minimum rated circuit breaker of 20 amperes, and not to exceed the wire rating of the
facility.
13. For high-voltage, three phase installations (380 V to 415 V), IBM recommends a
minimum rated circuit breaker of 15 amperes, and not to exceed the wire rating of the
facility.
62
ESS Introduction and Planning
Summary of Contents for Enterprise Storage Server 2105 E10
Page 2: ......
Page 8: ...vi ESS Introduction and Planning ...
Page 10: ...viii ESS Introduction and Planning ...
Page 12: ...x ESS Introduction and Planning ...
Page 14: ...xii ESS Introduction and Planning ...
Page 22: ...xx ESS Introduction and Planning ...
Page 24: ...xxii ESS Introduction and Planning ...
Page 48: ...24 ESS Introduction and Planning ...
Page 72: ...48 ESS Introduction and Planning ...
Page 88: ...64 ESS Introduction and Planning ...
Page 108: ...84 ESS Introduction and Planning ...
Page 112: ...88 ESS Introduction and Planning ...
Page 118: ...94 ESS Introduction and Planning ...
Page 155: ......