Table 54. DS8000 input voltages and frequencies
Characteristic
Low Voltage
High voltage feature
Nominal input voltages
200, 208, 220, or 240 RMS V
ac
380, 400, 415, or 480 RMS V
ac
Minimum input voltage
180 RMS V ac
333 RMS V ac
Maximum input voltage
264 RMS V ac
508 RMS V ac
Customer wall breaker rating
(1-ph, 3-ph)
50-60 Amps
30-35 Amps
Steady-state input
frequencies
50 ± 3 or 60 ± 3.0 Hz
50 ± 3 or 60 ± 3.0 Hz
PLD input frequencies (<10
seconds)
50 ± 3 or 60 ± 3.0 Hz
50 ± 3 or 60 ± 3.0 Hz
Power connector requirements
Ensure that the site where you plan to install the DS8000 storage units meets the
power connector requirements.
Table 55 provides the power cords and the inline connectors and receptacles types
that they support. Find the power cord row that is appropriate for your site.
Ensure that the site where you plan to install the DS8000 storage units meets the
power connector requirements that are shown in that row.
Phase rotation on 3-phase power-cable connectors is counterclockwise as you look
at the power cord plug. Phase rotation is clockwise as you look at the face of the
power receptacle at your installation site.
Attention:
v
Low-voltage, three-phase installations (200-240 V) require wall circuit breakers
that have a rating of 50 to 60 A.
v
High-voltage, three-phase installations (380-480 V) require wall circuit breakers
that have a rating of 30 to 35 A.
Note:
Special applications that use 30 A power cords must rely on 30 A wall
circuit breakers for power cord protection.
Do not exceed the wire rating of the facility.
Table 55. DS8000 power cords
Power Cord Feature Code
Power Cord
Description
Inline Connector
Receptacle
1060
(see Notes 1, 2,
3, 5, and 8.)
Power cord for U.S.,
Canada, LA, and AP:
Single-phase, 50 Hz or
60 Hz, 60 amperes
IEC 309
IEC 309
1067
(see Notes 1, 2,
5, and 8.)
Power cord for EMEA:
1-phase 50 Hz 35
amperes
Not applicable
Hard-wired
1090
(see Notes 1, 2,
3, and 5.)
Power cord for U.S.,
Canada, LA, and AP:
3-phase 50 Hz or 60
Hz, 60 amperes
7428-78 (see Note 7.) 7324-78
162
Introduction and Planning Guide
Summary of Contents for DS8700
Page 2: ......
Page 8: ...vi Introduction and Planning Guide...
Page 10: ...viii Introduction and Planning Guide...
Page 20: ...xviii Introduction and Planning Guide...
Page 22: ...xx Introduction and Planning Guide...
Page 44: ...22 Introduction and Planning Guide...
Page 142: ...120 Introduction and Planning Guide...
Page 160: ...138 Introduction and Planning Guide...
Page 212: ...190 Introduction and Planning Guide...
Page 218: ...196 Introduction and Planning Guide...
Page 224: ...202 Introduction and Planning Guide...
Page 242: ...220 Introduction and Planning Guide...
Page 254: ...232 Introduction and Planning Guide...
Page 255: ......
Page 256: ...Printed in USA GC27 2297 09...