32.
Perform the following steps for each entry in the list of A
xx
partitions you began recording in step
14 on page 85, except the partition you were using to debug the original problem.
33.
From the IVM virtual terminal window of a partition in the list of A
xx
partitions, type
diag
at the
AIX command prompt.
34.
When the diagnostic operating instructions are displayed, do the following steps:
1.
Press Enter.
2.
Select the
Task Selection
option.
Note:
If the terminal type is not defined, you are prompted to
define it before you can proceed.
3.
Select the
Log Repair
option.
4.
Select the resource associated with the repair action. If the repair
action was reseating a cable or adapter, select the resource
associated with that repair action. If the resource associated with
your repair action is not displayed on the Resource List, select
sysplanar0
.
5.
Click
Commit
after you have made your selection.
35.
Exit from diagnostics in this partition and return to the AIX command prompt.
36.
Have all the partitions in the list of A
xx
partitions you began recording in step 14 on page 85 been
processed?
v
Yes:
Continue with the next step.
v
No:
Go to step 32 to process the next partition in the list you recorded in step 14 on page 85.
37.
If the system attention LED is still on, turn off the LED as described in “Activating and deactivating
LEDs.” This completes the repair. Return the system to the customer.
Note:
If, during the processing of the list of open service action events, some service action events remained open,
further service actions might be required to complete the repair.
Activating and deactivating LEDs
You can use these procedures to activate or deactivate light-emitting diodes (LEDs) using the
management console or the Advanced System Management Interface (ASMI).
For IBM Power Systems servers that contain the POWER7 processor, the LEDs can be used to identify or
verify a part that you are servicing. The error and identify function (amber) LED indicates an error and
corresponds to the location code in the system reference code (SRC). The LED is activated and
deactivated automatically.
Additionally, the following procedures can also be used to activate and deactivate LEDs.
v
“Deactivating a system attention LED or partition LED using the management console” on page 88
v
“Activating or deactivating an identify LED using the management console” on page 88
v
“Deactivating a system attention LED or logical partition LED using the Advanced System
Management Interface” on page 89
Power supplies
87
Summary of Contents for 9117-MMB
Page 1: ...Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 2: ......
Page 3: ...Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 112: ...100 Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 113: ......
Page 114: ... Printed in USA ...