18.
Click
Close Event
.
19.
Add comments for the serviceable event. Include any unique additional information. Click
OK
. The
following steps will add or update FRU information.
20.
Did you replace, add, or modify a FRU of the open service action event?
v
Yes:
Continue with the next step.
v
No:
Go to step 22.
21.
From the FRU list, select a FRU that you need to update. Double-click the FRU, and update the FRU
information. Go to step 23.
22.
Select the
No FRU Replaced for this Serviceable Event
option.
23.
Click
OK
to close the service action event.
24.
Is the list of all partitions you recorded in step 11 on page 76 empty?
v
Yes:
Go to step 32 on page 78.
v
No:
Continue with the next step.
25.
Does the list of all partitions you recorded in step 11 on page 76 contain more than one entry?
v
Yes:
Continue with the next step.
v
No:
Go to step 32 on page 78.
26.
Is the error class recorded in step 25 AIX?
v
Yes:
Continue with the next step.
v
No:
Go to step 32 on page 78.
27.
Perform the following steps for each entry in the list of all partitions you recorded in step 11 on page
76, except the partition you were using to debug the original problem.
28.
From the HMC virtual terminal window of a partition in the list of all partitions, type
diag
at the
AIX command prompt.
29.
When the diagnostic operating instructions are displayed, do the following steps:
Power supplies
77
Summary of Contents for 9117-MMB
Page 1: ...Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 2: ......
Page 3: ...Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 112: ...100 Power Systems Power supplies for the 9117 MMB 9117 MMC 9179 MHB or 9179 MHC ...
Page 113: ......
Page 114: ... Printed in USA ...