Features and specifications
The following table provides a summary of the features and specifications of the
BladeCenter unit. Depending on the model, some features might not be available,
or some specifications might not apply.
Media tray (on front):
v
Optical drive (optional)
v
Two USB v2.0 ports
v
Front system LED panel
Blade bays (on front):
14 hot-swap
blade-server bays
Module bays (on front):
Four hot-swap
power-module bays
Module bays (on rear):
v
Two hot-swap management-module
bays
v
Ten hot-swap I/O-module bays
v
Two hot-swap blower bays
Power modules:
v
Minimum: Two hot-swap power
modules that are configured for
redundant operation
v
Maximum: Four hot-swap power
modules that provide redundancy to
all BladeCenter components
Redundant cooling:
Two
variable-speed hot-swap blowers
Management module:
v
Minimum: One hot-swap advanced
management module.
v
Maximum: Two hot-swap advanced
management modules: one active,
one hot stand-by.
Upgradeable microcode:
v
Management-module firmware
v
I/O-module firmware (not all I/O
module types)
v
Blade-server firmware
Security features:
v
Login password for remote connection
v
Secure Sockets Layer (SSL) security for
remote management access
Predictive Failure Analysis (PFA) alerts:
v
Blowers
v
Blade-dependent features
Size (9 U):
v
Height: 400.1 mm (15.75 in. or 9 U)
v
Depth: 711.2 mm (28 in.)
v
Width: 482.6 mm (19 in.)
v
Weight:
– Full configured weight with blade
servers: Approximately 158.8 kg (350
lbs)
– Empty chassis without modules or
blade servers: Approximately 40.82
kg (90 lbs)
Environment:
v
Air temperature:
– BladeCenter unit on:
- Altitude: 0 to 914 m (3000 ft)
10° to 35°C (50° to 95°F)
- Altitude: 914 m to 2134 m (3000 ft to
7000 ft) 10° to 32°C (50° to 90°F)
– BladeCenter unit off: -40° to 60°C
(-40° to 140°F).
v
Humidity: 8% to 80%
v
Acoustics: declared sound power level: 7.5
bels
1
Electrical input:
v
Sine-wave input (50-60 Hz single-phase)
required
v
Input voltage:
– Minimum: 200 V ac
– Maximum: 240 V ac
Heat output:
Approximate heat output in
British thermal units (Btu) per hour:
v
Minimum configuration: 1024 Btu/hour
(300 watts)
v
Maximum configuration: 32757 Btu/hour
(9600 watts)
Airflow:
Approximate airflow in cubic feet
per minute (cfm):
v
Minimum airflow: 450 cfm
v
Maximum airflow: 975 cfm
Notes:
1.
Government regulations (such as those prescribed by Occupational Safety and Health Administration or European Community
Directives) might govern noise level exposure in the workplace and might apply to you and your server installation. The actual
sound pressure levels in your installation depend on a variety of factors, including the number of racks in the installation; the
size, materials, and configuration of the room where you designate the racks to be installed; the noise levels from other
equipment; the room ambient temperature; and employees' location in relation to the equipment. Compliance with such
government regulations also depends on a variety of additional factors, including the duration of employees' exposure and
whether employees wear hearing protection. It is recommended that you consult qualified experts in this field to determine
whether you are in compliance with the applicable regulations.
4
BladeCenter H Type 8852, 7989, and 1886: Problem Determination and Service Guide
Summary of Contents for 8852 - BladeCenter H Rack-mountable
Page 1: ...BladeCenter H Type 8852 7989 and 1886 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...BladeCenter H Type 8852 7989 and 1886 Problem Determination and Service Guide...
Page 24: ...10 BladeCenter H Type 8852 7989 and 1886 Problem Determination and Service Guide...
Page 36: ...22 BladeCenter H Type 8852 7989 and 1886 Problem Determination and Service Guide...
Page 84: ...70 BladeCenter H Type 8852 7989 and 1886 Problem Determination and Service Guide...
Page 87: ......
Page 88: ...Part Number 81Y1107 Printed in USA 1P P N 81Y1107...