Risks that are posed by the presence of excessive particulate levels or
concentrations of harmful gases include damage that might cause the device to
malfunction or cease functioning altogether. This specification sets forth limits for
particulates and gases that are intended to avoid such damage. The limits must not
be viewed or used as definitive limits, because numerous other factors, such as
temperature or moisture content of the air, can influence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of
specific limits that are set forth in this document, you must implement practices
that maintain particulate and gas levels that are consistent with the protection of
human health and safety. If IBM determines that the levels of particulates or gases
in your environment have caused damage to the device, IBM may condition
provision of repair or replacement of devices or parts on implementation of
appropriate remedial measures to mitigate such environmental contamination.
Implementation of such remedial measures is a customer responsibility.
Table 6. Limits for particulates and gases
Contaminant
Limits
Particulate
v
The room air must be continuously filtered with 40% atmospheric dust
spot efficiency (MERV 9) according to ASHRAE Standard 52.2
1
.
v
Air that enters a data center must be filtered to 99.97% efficiency or
greater, using high-efficiency particulate air (HEPA) filters that meet
MIL-STD-282.
v
The deliquescent relative humidity of the particulate contamination
must be more than 60%
2
.
v
The room must be free of conductive contamination such as zinc
whiskers.
Gaseous
v
Copper: Class G1 as per ANSI/ISA 71.04-1985
3
v
Silver: Corrosion rate of less than 300 Å in 30 days
1
ASHRAE 52.2-2008 -
Method of Testing General Ventilation Air-Cleaning Devices for
Removal Efficiency by Particle Size
. Atlanta: American Society of Heating, Refrigerating
and Air-Conditioning Engineers, Inc.
2
The deliquescent relative humidity of particulate contamination is the relative
humidity at which the dust absorbs enough water to become wet and promote ionic
conduction.
3
ANSI/ISA-71.04-1985.
Environmental conditions for process measurement and control
systems: Airborne contaminants
. Instrument Society of America, Research Triangle Park,
North Carolina, U.S.A.
Telecommunication regulatory statement
This product may not be certified in your country for connection by any means
whatsoever to interfaces of public telecommunications networks. Further
certification may be required by law prior to making any such connection. Contact
an IBM representative or reseller for any questions.
Electronic emission notices
When you attach a monitor to the equipment, you must use the designated
monitor cable and any interference suppression devices that are supplied with the
monitor.
Appendix C. Notices
49
Summary of Contents for 5594-1AX
Page 1: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 2: ......
Page 3: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 6: ...iv Installation and User s Guide...
Page 20: ...4 Installation and User s Guide...
Page 34: ...18 Installation and User s Guide...
Page 52: ...36 Installation and User s Guide...
Page 58: ...42 Installation and User s Guide...
Page 62: ...46 Installation and User s Guide...
Page 69: ...Taiwan Class A compliance statement Appendix C Notices 53...
Page 70: ...54 Installation and User s Guide...
Page 72: ...56 Installation and User s Guide...
Page 73: ......
Page 74: ...Part Number 47C9191 Printed in USA 1P P N 47C9191...