5594-1KX
5594-2KX
5594-3KX
AC Output power
50/60Hz, 1ph;
200VAC, 1550VA,
1100W, 7.5A;
208VAC, 1550VA,
1100W, 7.3A;
220VAC, 1550VA,
1100W, 6.9A;
230VAC, 1550VA,
1100W, 6.6A;
240VAC, 1550VA,
1100W, 6.3A
50/60Hz, 1ph;
200VAC, 1700VA,
1530W, 8.5A;
208VAC, 1980VA,
1780W, 9.5A;
220VAC, 2200VA,
1980W, 10.0A;
230VAC, 2200VA,
1980W, 9.6A;
240VAC, 2200VA,
1980W, 9.2A
50/60Hz, 1ph;
200VAC, 2700VA,
2430W, 13.5A;
208VAC, 3000VA,
2700W, 14.5A;
220VAC, 3000VA,
2700W, 13.7A;
230VAC, 3000VA,
2700W, 13.0A;
240VAC, 3000VA,
2700W, 12.5A
Output on battery
power
v
Voltage
v
Frequency
230 V (-10/+6 %)
(1)
50/60 Hz ±0.1 Hz
Battery (sealed lead
acid, maintenance
free)
v
Standard
v
Additional
modules possible
(up to 4 EBMs)
4 x 12 V
7.2 Ah
4 x 12 V
9 Ah
6 x 12V
9Ah
5594-2BX
(2)
5594-3BX
(3)
Environment
Operating temperature: 0 to +40 °C (32 to 104 °F)
Storage temperature: -15 to +50 °C (5 to 122 °F)
Relative humidity: 20 to 90 % (without condensation)
Noise level: < 45 dBA
Noise level: < 50 dBA
(1)
Adjustable to 200/208/220/230/240 V (23 % derating at 200 V, 10 % derating at 208 V on 2.2 kVA, and 17 % derating at 200 V
on 3 kVA).
(2)
5594-2BX
: 2 strings, each 4 x 12 V / 9 Ah.
(3)
5594-3BX
: 2 strings, each 6 x 12 V / 9 Ah.
Appendix A. Specifications
41
Summary of Contents for 5594-1AX
Page 1: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 2: ......
Page 3: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 6: ...iv Installation and User s Guide...
Page 20: ...4 Installation and User s Guide...
Page 34: ...18 Installation and User s Guide...
Page 52: ...36 Installation and User s Guide...
Page 58: ...42 Installation and User s Guide...
Page 62: ...46 Installation and User s Guide...
Page 69: ...Taiwan Class A compliance statement Appendix C Notices 53...
Page 70: ...54 Installation and User s Guide...
Page 72: ...56 Installation and User s Guide...
Page 73: ......
Page 74: ...Part Number 47C9191 Printed in USA 1P P N 47C9191...