5594-1AX
5594-2AX
5594-3AX
Environment
Operating temperature: 0 to +40 °C (32 to 104 °F)
Storage temperature: -15 to +50 °C (5 to 122 °F)
Relative humidity: 20 to 90 % (without condensation)
Noise level: < 45 dBA
Noise level: < 50 dBA
(1)
Adjustable to 100 V (17 % derating at 100 V on 1.5 kVA / 3 kVA, 32 % derating at 100 V on 2.2 kVA) 120/125 V.
(2)
5594-2BX
: 2 strings, each 4 x 12 V / 9 Ah.
(3)
5594-3BX
: 2 strings, each 6 x 12 V / 9 Ah.
When the appliance is used in the EU, use an external circuit breaker in front of
line with rating 16 A, 250 V which is IEC/EN 60898-1 standard compliant.
When the appliance is used in American area, use an external circuit breaker in
front of line with rating 20 A, 250 V.
This product is designed for IT power distribution systems.
Technical specifications: 200V/230V models
The IBM 2U Rack or Tower UPS, 200V model and 230V model, is a single-phase
UPS unit.
5594-1KX
5594-2KX
5594-3KX
Output Power
1500 VA
1350 W
2200 VA
1980 W
3000 VA
2700 W
AC Input power
200-240VAC,
50/60Hz, 1ph, 10A
max
200-240VAC,
50/60Hz, 1ph, 16A
max
200-240VAC,
50/60Hz, 1ph, 16A
max
40
Installation and User's Guide
Summary of Contents for 5594-1AX
Page 1: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 2: ......
Page 3: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 6: ...iv Installation and User s Guide...
Page 20: ...4 Installation and User s Guide...
Page 34: ...18 Installation and User s Guide...
Page 52: ...36 Installation and User s Guide...
Page 58: ...42 Installation and User s Guide...
Page 62: ...46 Installation and User s Guide...
Page 69: ...Taiwan Class A compliance statement Appendix C Notices 53...
Page 70: ...54 Installation and User s Guide...
Page 72: ...56 Installation and User s Guide...
Page 73: ......
Page 74: ...Part Number 47C9191 Printed in USA 1P P N 47C9191...