![IBM 5594-1AX Installation And User Manual Download Page 33](http://html1.mh-extra.com/html/ibm/5594-1ax/5594-1ax_installation-and-user-manual_3372202033.webp)
Table 1. User settings (continued)
Submenu
Available settings
Default settings
Battery settings
Automatic battery
test
[No test] [Every day]
[Every week] [Every
month]
Available only if
battery charge mode
is set to constant
charge.
Every week (in
constant charge)
otherwise following
ABM
Low battery warning [10 %] [20 %] [30 %]
[40 %] [50 %] [60 %]
[70 %] [80 %] [90 %]
The alarm triggers
when the set
percentage of battery
capacity is reached
during a back-up
time.
[20%]
Restart battery level
[10 %] [20 %] [30 %]
[40 %] [50 %] [60 %]
[70 %] [80 %] [90 %]
[100 %]
If set, automatic
restart will occur
only when
percentage of battery
charge is reached.
[0%]
Battery charge mode
[ABM cycling]
[Constant charge]
[ABM cycling]
EBM number setting
[0] [1] [2] [3] [4]
Using standard EBM,
UPS detects
automatically the
amount of EBM
connected.
EBM automatic
detection, otherwise
[0]
Deep discharge
protection
[Yes] [No]
If set to Yes, the UPS
automatically
prevents battery from
deep discharge by
adapting end of
back-up time voltage
threshold.
[Yes]
Chapter 2. Presentation
17
Summary of Contents for 5594-1AX
Page 1: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 2: ......
Page 3: ...IBM 2U Rack or Tower UPS RT1 5kVA RT2 2kVA and RT3 0kVA Installation and User s Guide...
Page 6: ...iv Installation and User s Guide...
Page 20: ...4 Installation and User s Guide...
Page 34: ...18 Installation and User s Guide...
Page 52: ...36 Installation and User s Guide...
Page 58: ...42 Installation and User s Guide...
Page 62: ...46 Installation and User s Guide...
Page 69: ...Taiwan Class A compliance statement Appendix C Notices 53...
Page 70: ...54 Installation and User s Guide...
Page 72: ...56 Installation and User s Guide...
Page 73: ......
Page 74: ...Part Number 47C9191 Printed in USA 1P P N 47C9191...