
8.3.3 Miscellaneous issues
Miscellaneous issues
Issue
Diagnosis
Fix
Fumes and
High
Humidity
Improperly installed
condensate trap
Refer to installation/operation instructions.
Leak in vent piping
Inspect using soap solution.
Flue gas leak within
boiler
Visually inspect all mechanical connections.
‘Ghost’ call
for heat.
Triac or ‘Power-
robbing’ thermostat
sending current to
boiler.
Remove Therm. connections from boiler to confirm that
stray voltage, or current induced in thermostat wiring, is
source of nuisance signal. Replace the Power Robbing
thermostat, isolate the thermostat with a relay or install a
properly sized resistor (consult the thermostat
manufacturer first then IBC for instructions).
Error: Water
High Limit /
Low Water
Cutoff won’t
clear.
Boiler is in 1-hour
safety lockout.
For instructions on clearing errors, see
boiler after a hi-limit temperature lockout on page 107
and
Resetting a boiler after a LWCO lockout on page
.
DHW taking
too long to
heat.
Sensor may be under-
reading actual water
temp.
Check sensor engagement; note well is 15 cm / almost 6
inches deep and sensor must be fully set to back. Check
programmed settings boiler temp set too close to the
required DHW temperature.
Boiler output
not
modulating
up to
maximum
despite
target not
being
reached.
Possible flow issue:
check for 35 or 40 °F
temperature
difference between
boiler supply and
return water
temperatures (evokes
electronic fence).
Confirm that primary pump is able to overcome head
loss of boiler and primary loop piping at the required flow
rate.
Primary
Pump runs
but load
pumps do
not.
Wiring not complete.
Supply power to the PV/L and PV/N terminals from the
incoming power supply to the boiler. (Factory wired on
boilers with a factory installed touchscreen controller)
112
Section: Troubleshooting
Summary of Contents for CX Series
Page 10: ...Intentionally left empty...
Page 70: ...Intentionally left empty...
Page 84: ...Intentionally left empty...
Page 102: ...Intentionally left empty...
Page 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Page 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Page 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...