SIM Status Indicators
LED 1
LED 2
State
Description, LED status
indication
Rapid flash
Power up or
resetting
startup checks and initialization
Off
Off
Standby
LED 1 Off=flame or sparking
LED 2 = Burner-on call state
Off
On
Pre-purge or
inter-purge
LED 1 Off=no flame or sparking
LED 2 = Burner-on call state
On
On
Heating
LED 1 On = Flame detected
LED 2 = Burner-on call state
Rapid flash
On
Igniting
LED 1 Flashing - Electrode sparking
LED 2 = Burner-on call state
Off
Flashing
Lockout
Possible errors:
An operating limit was
exceeded
A sequence failed
An external sensor fault was
detected.
Flash alternately
with LED 2
Flash alternately
with LED 1
Fail-safe
An error was detected - the boiler
requires a power cycle
Table 12
SIM+ LED status Indicators
8.1.5.2 Resetting a boiler after a LWCO lockout
A boiler in a lockout condition due to a LWCO error will need to be reset.
1. Go to
>
Clear Errors
>
Yes
.
2. Check that there is enough water in the system and that the boiler is pressurized.
3. To reset the boiler, go to
>
SIM Menu
>
LWCO Test
>
Reset
>
Yes
.
4. Run the boiler to ensure that the error has been cleared.
106
Section: Troubleshooting
Summary of Contents for CX Series
Page 10: ...Intentionally left empty...
Page 70: ...Intentionally left empty...
Page 84: ...Intentionally left empty...
Page 102: ...Intentionally left empty...
Page 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Page 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Page 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...