8.2.4 Aux. Interlock 1 or 2
Aux. Interlock 1 or 2
Issue
Diagnosis
Fix
Interlock 1 or 2
terminals are open.
Jumper lead is loose
or compromised.
Replace the jumper lead.
External safety is in an
alarm state.
Inspect the external safety devices.
8.3 Miscellaneous touchscreen controller errors
Miscellaneous errors
Issue
Diagnosis
Fix
“ Loop/Indoor Sensor”
“Insufficient Air Flow”
“Insufficient Water
Pressure”
The sensor plug is not
engaged.
Check the P501 plug is fully engaged in the
back of the controller board.
“Unknown Error”
The sensor plug is not
engaged.
Check the P501 plug is fully engaged in the
back of the controller board.
Temperature sensor
input problem.
Test each temperature sensor for appropriate
readings and Replace defective temperature
sensor.
Error - Max.
Inlet/Outlet Sensor
Temp. Exceeded. >
Check water flow
Water temperature
signal not within
acceptable range.
Potential flow or
sensor failure. Consult
service technician.
Current outlet
temperature exceeds
operating limit.
Check water flow.
Defective or
disconnected
temperature sensor.
Check wiring to temperature sensor and
control module.
Check temperature sensor.
Blank – screen dark,
but fan running
Indicative of power-
surge damage to
appliance
Check transformer; replace if damaged.
Check circuit board for visible damage.
Controller is stuck in
If update fails or no
Restarting returns the boiler to normal
109
8.2.4 Aux. Interlock 1 or 2
Summary of Contents for CX Series
Page 10: ...Intentionally left empty...
Page 70: ...Intentionally left empty...
Page 84: ...Intentionally left empty...
Page 102: ...Intentionally left empty...
Page 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Page 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Page 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...