Start-up Checklist
Check
Tested efficiency of the appliance and made necessary adjustments by
combustion test and adjustment
.
□
Tested the low water cutoff function to check that the LWCO sensor is working. See
Testing the LWCO function on page 82
.
□
Tested the high limit temperature function to check that the High limit temperature sensor
is working. See
Testing the Hi-Limit cutoff temperature function on page 83
□
6.2 Testing the ignition safety shutoff
To test the ignition system safety shutoff function:
1. With the boiler in operation, shut off the gas control valve directly outside the boiler case.
2. Ensure that the boiler has purged, attempted to re-light three times, has shut off and the
appropriate error information is displayed on the controller.
3. The error is displayed after testing the ignition safety shutoff.
4. To restart the boiler, reset the power or on the
touchscreen controller
tap
(Status)>
Clear Errors
>
Yes
.
6.3 Commissioning
The appliances are factory calibrated to operate with natural gas (or propane if desired) at sea
level. The gas-air ratio or zero-offset adjustment screw may need adjusting to attain optimum
combustion results. Note that only qualified technicians using properly functioning and calibrated
combustion analyzing equipment should perform a mixture adjustment.
76
Section: Boiler operation
Summary of Contents for CX Series
Page 10: ...Intentionally left empty...
Page 70: ...Intentionally left empty...
Page 84: ...Intentionally left empty...
Page 102: ...Intentionally left empty...
Page 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Page 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Page 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...