Define the local variables and call up FC105 and SFC15 (both blocks from S7
standard library) in OB1 or any other FC.
The scaled temperature (0.0 - 700.0 °C) is saved as a REAL-value
in DB 11.DBD8 (the first memory range for analog signals)!
Figure 16:
Example how to transfer a consistent range of 32 byte from S7 PLC
(DB11) to DPM64 using SFC15
3.
In your program you have to adjust the peripheral output-address in network 3
(LADDR-parameter) with the DP output addresses in the HW-configuration (column
Q Address).
Note
Do not forget the offset of the data set in the Profibus message.
Example: In order to address the first analog value in mode 3, please consider an off-
set of 8 Bytes / 4 Words.
For more information see chapter „Output data “, page 29