6.4 Parameter function descriptions
6-11
6. Parameter
s
Parameter No.6: Current control setting at stop
No. Category
Name
Symbol
Unit
Input range Default setting
at shipping
6
A
Current control
setting at stop
SMOD
-
Disabled:
Powerful stop
Enabled:
Energy-saving
stop
Disabled
● The control method for ELECYLINDER stop can be selected.
● If [Disabled], a constant current value will be transmitted to the motor, stopping it.
This limits fine vibration when stopping, bringing the unit to a complete stop.
● If [Enabled], a current appropriate to the load will be transmitted to the motor, stopping it.
This limits the amount of power consumed while stopping.
● If abnormal noise or vibration occurs during a gradual stop, setting to [Enabled] may fix
the issue. Moreover, setting to [Enabled] can also fix issues in which the command
position cannot quite be attained.
Caution
If [Disabled], even if a pulse deviation within ±2 from the target position remains,
movement towards the target position will not continue.
If [Enabled], if a pulse deviation of ±1 or more from the target position remains,
movement towards the target position will continue.
Summary of Contents for EC-ST15
Page 2: ......
Page 26: ...Intro 18 ...
Page 28: ......
Page 44: ......
Page 60: ...2 16 2 Installation ...
Page 62: ......
Page 82: ...3 20 3 Wiring ...
Page 106: ......
Page 112: ...5 6 5 Preventive Predictive Maintenance ...
Page 114: ......
Page 128: ...6 14 6 Parameters ...
Page 130: ......
Page 148: ...7 18 7 Troubleshooting ...
Page 150: ......
Page 190: ...8 40 8 Maintenance and Inspection ...
Page 192: ......
Page 194: ...9 2 9 External Dimensions ...
Page 196: ......
Page 198: ...10 2 10 Life ...
Page 200: ......
Page 203: ...Appendix 12 1 Index 12 1 12 2 Revision history 12 4 ELECYLINDER Chapter12 ...
Page 204: ......
Page 209: ......