58
4. MSEL
4.4 Parameter Settings
Set to the I/O parameters in the controller by using a teaching tool.
Set the mode switchover switch on the front panel to MANU side.
The teaching tool version applicable for MSEL is as shown below:
•
XSEL PC software
:
V
10.00.09.00 to
•
TB-01 [MSEL-PCX/PGX] :
V1.
02 to
•
TB-01 [MSEL-PC(F)/PG(F)] :
V1.10
to
•
TB-02
:
V1.
00 to
㻌
㻌
[1] Network Setting Check
Confirm that the
I/O Parameter No. 225 Network I/F Module Control setting is showing “
2
”
(DeviceNet).
(The setting of this parameter is to be established before delivery)
No.
Parameter name
Default
Input Range
Unit
Remarks
225 Extension I/O Control
*2
2
H
-
Bits 0-3(First digit):
I/O2 module type
0: Not Mounted
1:CC-Link
2:DeviceNet
3:PROFIBUS
[2] DeviceNet Board Use Setting
Have I/O P
arameter No. 18 set to “1” (Monitor: use
DeviceNet board).
No.
Parameter name
Default
(Reference) Input Range
Unit
Remarks
18 I/O2 Error Monitoring
1
0 to 5
-
0: No Monitoring
(Not to use DeviceNet board)
1: Monitoring
[3] Node address setting
Have the node address set in I/O Parameter No. 226.
No.
Parameter name
Default
(Reference) Input Range
Unit
Remarks
226 I/O2 F
ieldbus
Node Address
0
0 to 63
-
DeviceNet node address range:
0 to 63
Note If a number
out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.