The response of Table 12 will confirm this request:
UNIT I/D
FUNCTION
COIL ADDRESS
FORCE COIL
CRC
01
05
High
Low
High
Low
High
Low
00
00
ff
00
nn
nn
Table 12: Returned Information from DSP Following a Force Bit Request
The registers can be read either one at a time or in a continuous block up to a maximum of 100 registers at a time.
There are times when the DSP processor will not be able to respond to a request since it is busy with other tasks and
no response will be returned. For this reason it is recommended to request the maximum number of registers used
by the system in a single request. Since the DSP is set up to 50 current registers, 50 status registers and 50 priority
registers followed by the system function registers, it is best to read the data with three consecutive requests.
Note: The DSP will not respond to requests if the DSP-DM is in the SETUP mode.
The feeder module currents IGf values are contained in the first 50 registers as follows. The values range from 0x00
to 0xff although maximum for a first fault condition will be 0x64 or 100%. Table 8 lists the register addresses in the
MODBUS convention.
REGISTER NO.
CONTENTS
FORMAT
40001
Feeder 1 I gf
0x00 nn
40002
Feeder 2 I gf
40003
Feeder 3 I gf
Feeder Module Status is represented by five valid states as follows:
0x00 = OK
0x01 = Faulted Feeder
0x02 = Feeder Tripped
0x03 = Test Button Pushed
0x0f = Not available
The following registers return two bytes – The first byte is always 0x00 with the second returning status in hexadeci
-
mal as above.
Table 13: Feeder Module Ground Current Addresses
REGISTER NO
CONTENTS
FUNCTION
FORMAT
40051
Feeder 1 Status
0x00 nn
40052
Feeder 2 Status
40053
Feeder 3 Status
Table 14: Feeder Module Status Addresses
REGISTER NO
CONTENTS
FUNCTION
FORMAT
40101
Feeder 1 Priority
0x00nn
40102
Feeder 2 Priority
Table 15: Feeder Module Priority Addresses
Summary of Contents for DSP-OHMNI
Page 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Page 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Page 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Page 45: ...43 Figure 41 DSP DPS System Module Connection ...
Page 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Page 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Page 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...