26
safely isolated and removed.
If pulsing is selected ON, then it will remain ON until turned OFF again or RESET is pressed. The home screen has a
Pulse signal indicator to remind the operator that pulsing is ON with the screen of Figure 26.
Figure 26: New Home Screen indicates Pulsing ON
12V DC Pulse current is sent from the DSP-DPS ‘+’ and ‘-’ terminals to the DSP-OHMNI-PM neutral grounding resis-
tor to energize the solid-state relay in the OHMNI-PM to modulate the ground fault current (if any). When finished with
the pulse operation, press the home button to exit and return to the home screen.
Alarm Indications
If a fault greater than the alarm level setting develops somewhere on the system, or the (optional) DSP-DRM resistor
monitor detects a neutral grounding resistor failure, an alarm is declared by the system module. Alarms are annunci-
ated in three ways:
1. LED Indications
- DSP-DSM system module red ALARM light
- DSP-DFM fault indication is enabled to provide indication if fault is detected by feeder module (the fault may
not be detected by a feeder module. For example, if it is on the main bus it won't be detected).
2. Alarms
DSP-DRM red light (NGR FAULT) lights.
Alarm relay (Form C) on DSP-DPS will operate to energize customers’ alarm device (horn etc.)
A local beeper will sound in the DSP-TDM to indicate the fault.
The alarms both local and external can be cancelled by the MUTE button, which is the key on the Home
screen. Once cancelled, the alarm will remain off until the MUTE Delay times out from the moment of the last initia-
tion of the MUTE command, and if an alarm condition still exists. RESET will also cancel the MUTE effect. The MUTE
control of the alarm relay contacts may be disabled to allow use of the ALARM contacts in the DSP-DPS power supply
to be used for other purposes than an audible horn (fans for example). However, the MUTE in that case would still
silence the local beeper.
Summary of Contents for DSP-OHMNI
Page 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Page 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Page 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Page 45: ...43 Figure 41 DSP DPS System Module Connection ...
Page 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Page 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Page 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...