37
UNIT I/D
FUNTION STARTING ADDRESS
3 OF REGISTERED REG.
CRC
01
03
High
Low
High
Low
High
Low
00
01
00
02
nn
nn
Table 8: Modbus RTU Standard 8 Byte Holding Register Read Function (o3)
DSP MODBUS Output Structure
Two functions are supported: Read Holding Register (03) and Set Coil (05)
There are 156 registers available, which can be accessed by an external host system. This document summarizes the
format and function of these registers. The request from the master is always 8 bytes long and are as shown in table 8
below.
All bytes are in hexadecimal. Numbers above are, for example, a request for 2 registers only, starting from address 01.
CRC check sum is 16 bit CRC as described in MODBUS information. The high bytes are not used in any requests. If
successful, the DSP will return the message shown in table 9 below.
UNIT I/D
FUNTION
# OF
BYTES
Data 1
DATA 2
CRC
01
03
04
High
Low
High
Low
Low
High
Low
00
nn
00
nn
nn
nn
nn
Table 9: Returned Information Structure for Holding Register Request
Register contents are shown in Tables 13 to 16.
Note: Register number is shown in decimal but must be sent in hexadecimal form in the request. The only write func-
tions presently supported in the DSP system are RESET control and PULSE ON/OFF which will require the use of set
coil function in MODBUS. The format for setting is as shown in Table 8.
UNIT I/D
FUNTION
COIL ADDRESS
FORCE COIL
CRC
01
05
High
Low
High
Low
High
Low
00
00
ff
00
nn
nn
Table 10: Request to Write to Set a Bit on a Register (MODBUS Force Coil)
In this case there will only be two ‘coils’ (actually DSP functions).
COIL NO
NAME
FORCE COIL DATA
0
Reset
ff00=on
0000=off
1
Reset
ff00=on
0000=off
Table 11: Write Register Information
Summary of Contents for DSP-OHMNI
Page 1: ...C EG30EM Instruction Manual V2 June 2020 DSP OHMNI ...
Page 11: ...9 Figure 1b DSP DCM Wiring Figure 1c System Module DSP DSM Wiring ...
Page 12: ...10 Figure 1d Power Supply DSP DPS Wiring Figure 2 Preferred Feeder Module DSP DFM Wiring ...
Page 45: ...43 Figure 41 DSP DPS System Module Connection ...
Page 46: ...44 Figure 43 DSP DLM Logging Module Connections Figure 44 DSP TDM Display Module Connections ...
Page 47: ...45 Figure 45 Typical DSP DRM Installation Connections ...
Page 50: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com ...