9.5 Maintenance scheme
9.5.1 Daily maintenance
»
Check if the system is working cor-
rectly.
»
Check that there are no leaks in the
water-carrying components.
»
Check the water inlet pressure.
The system supply pressure (after the pre-fil-
ters) must be at least 2 bar during normal
operation. Replace the filter cartridges if the
pressure loss is too high.
9.5.2 Weekly maintenance
»
Check the max. membran pressure
(max.10 bar!).
»
Check the water conductivity of the
permeate with the control unit.
»
Note down the data for the listed
tests
•
Note that the production quantity of the
permeate increases with rising water
temperature, while the quality of Per-
meate is decreasing. Conversely, the
production quantity decreases with
decreasing temperature, while the
quality of the permeate improves.
•
The indication of the measured perme-
ate conductivity value on the display of
the control unit settles down to the
actual value within the first minutes.
9.5.3 Maintenance every two months
»
Check that there is not too much
free chlorine at the outlet (less than
0.25ppm).
Replace the pre-filter cartridge::
»
Every 2 months if the free chlorine
content is between 0.1 ppm and 0.2
ppm.
»
Every 4 months if the free chlorine
content is less than 0.1 ppm.
The lifetime of the pre-filter and membrane(s)
depends on feed water quality and permeate
production rate.
Maximum permitted storage times of the
membranes:
•
6 months: if the membranes are
already supplied with a chemical solu-
tion and/or impregnated with glycol;
•
1 year: if the membranes are supplied
dry or vacuum packed.
9.5.4 Maintenance by qualified per-
sonnel
every 6 months:
Check the pre-filling pressure of the expan-
sion vessel. This value must be 1.5 to 1.8
bar. To check the pressure, the outlet line of
the vessel must be temporarily interrupted.
Generally:
»
Check the parameters of the water
entering the system.
»
Check the conductivity of the input
water and permeate with a conduc-
tivity meter.
»
Record the data for the listed tests.
NOTICE
NOTICE
NOTICE
NOTICE
Summary of Contents for WL-ROL 160-1200 Series
Page 1: ...FlexLine Reverse osmosis plants MANUAL WLROL EN E 8881184 WLROL ENj WL ROL 160 1200...
Page 62: ...Page 62...
Page 65: ...Page 65 13 Declaration of Conformity...
Page 66: ...Page 66...
Page 72: ...Page 72 This page intentionally left blank...
Page 73: ...SPA Page 73 This page intentionally left blank...