- 21 -
6.5 About the limitation of water in temperature
Water in temperature
≦
7
℃
, the heat pump will stop operation.
Note : If the water filtration system is stop before the heat pump, the unit will down (security condition) and the
code EE3 or ON advertise on the controller.
It is important to program the heat pump link the time program of the water filtration system.
For restart the heat pump, turn off and turn on the electrical power supply to restart the unit.
7. Troubleshooting
7.1 Error code display on LED wire controller
Malfunction
Error code
Reason
Solution
Inlet water temperature sensor
failure
PP01
The sensor in open or short circuit
Check or change the sensor
Outlet water temperature
sensor failure
PP02
The sensor in open or short circuit
Check or change the sensor
Heating condenser sensor failure
PP03
The sensor in open or short circuit
Check or change the sensor
Gas return sensor failure
PP04
The sensor in open or short circuit
Check or change the sensor
Ambient temperature sensor
failure
PP05
The sensor in open or short circuit
Check or change the sensor
Condenser gas exit sensor failure
PP06
The sensor in open or short circuit
Check or change the sensor
Antifreeze protection in Winter
PP07
Ambient temperature or water inlet
temperature is too low
Low ambient temperature
protection
PP08
Ambient temperature or water inlet
temperature is too low
Ambient temperature is too in
heating mode
PP09
Ambient temperature is too high
Stop the heat pump and wait
the ambient temperature at
less than Air 40
℃
( less 5
℃
in
allowance) The error code will
disappear automatically
Cooling condenser temperature
too high protection
PP10
Cooling condenser temperature is
too high
Stop the heat pump and wait
the
cooling
condenser
temperature drop down
High pressure failure
EE01
1.Refrigerant is too much
2. Air flow is not enough
1.Discharge redundant
refrigerant from HP gas system
2.Clean the air exchanger
Low pressure failure
EE02
1.Refrigerant is not enough
2.Water flow is not enough
3. Filter jammed or capillary jammed
1.Check if there is any gas
leakage ,re
‐
fill the refrigerant
2.Clean the air exchanger
3.Replace the filter or capillary
Water flow failure
EE03 or
"ON"
Low water flow, wrong flow
direction, or flow switch failure.
Check if the water flow is
enough and flow in right
direction, or else the flow
switch could be failed.
Summary of Contents for Inverter 07
Page 1: ...Swimming Pool Heat Pump User and Service manual English French Dutch German Polish Danish ...
Page 2: ......
Page 4: ......
Page 8: ... 4 2 Dimension mm Model Inverter 7 10 Model Inverter 14 ...
Page 9: ... 5 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 17: ... 13 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 7 10 14 17 21 ...
Page 18: ... 14 5 2 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 26 35 ...
Page 19: ... 15 5 3 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 26T 35T ...
Page 36: ... 32 2 Dimension Modèle Inverter 7 10 Modèle Inverter 14 ...
Page 37: ... 33 Modèle Inverter 17 Modèle Inverter 21 26 26T 35 35T ...
Page 46: ... 42 5 2 SCHEMA DE CABLAGE DE POMPE À CHALEUR DE PISCINE Inverter 26 35 ...
Page 47: ... 43 5 3 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Inverter 26T 35T ...
Page 64: ... 60 2 Afmeting Dimension Model Inverter 7 10 Model Inverter 14 ...
Page 65: ... 61 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 73: ... 69 5 Elektrische bedrading 5 1 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 7 10 14 17 21 ...
Page 74: ... 70 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 26 35 ...
Page 75: ... 71 5 3 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 26T 35T ...
Page 92: ... 88 2 Ausmaße Model Inverter 7 10 Model Inverter 14 ...
Page 93: ... 89 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 102: ... 98 5 2 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Inverter 26 35 ...
Page 103: ... 99 5 3 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Inverter 26T 35T ...
Page 121: ... 117 2 Wymiary Model Inverter 7 10 Model Inverter 14 ...
Page 122: ... 118 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 131: ... 127 5 2 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Inverter 26 35 ...
Page 132: ... 128 5 3 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Inverter 26T 35T ...
Page 150: ... 146 2 Dimension mm Model Inverter 7 10 Model Inverter 14 ...
Page 151: ... 147 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 160: ... 156 5 2 SWIMMINGPOOL VARMEPUMPE WIRING DIAGRAM Inverter 26 35 ...
Page 161: ... 157 5 3 SWIMMINGPOOL VARMEPUMPE WIRING DIAGRAM Inverter 26T 35T ...
Page 175: ......
Page 176: ...A0111HYI04 ...