3.5 Typical arrangement
Note: This arrangement is only an illustrative example.
3.6 Adjusting the bypass
Optimal operation of the heat pump occurs when the cooling gas pressure is 22
2 bar.
This pressure can be read on the pressure gauge next to the control heat pump panel. Under these conditions the
water flow through the unit is also optimal.
Note: Operation without a bypass or with improper bypass adjustment may result in sub
‐
optimal heat pump
operation and possibly damage to the heat pump, which renders the warranty null and void.
Out
In
Heat Pump
Use the following procedure to adjust
the bypass:
fully open all three valves
slowly close valve 1 until the
water pressure is increased by
approximately 100 to 200 g
Close valve 3 approximately
half-way to adjust the gas
pressure in the cooling system
If the display shows "ON" or
error code EE3, close step by
step the valve 2, to increase
water flow and stop when the
code disappear.
To pool
From pool
Summary of Contents for Inverter 07
Page 1: ...Swimming Pool Heat Pump User and Service manual English French Dutch German Polish Danish ...
Page 2: ......
Page 4: ......
Page 8: ... 4 2 Dimension mm Model Inverter 7 10 Model Inverter 14 ...
Page 9: ... 5 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 17: ... 13 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 7 10 14 17 21 ...
Page 18: ... 14 5 2 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 26 35 ...
Page 19: ... 15 5 3 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 26T 35T ...
Page 36: ... 32 2 Dimension Modèle Inverter 7 10 Modèle Inverter 14 ...
Page 37: ... 33 Modèle Inverter 17 Modèle Inverter 21 26 26T 35 35T ...
Page 46: ... 42 5 2 SCHEMA DE CABLAGE DE POMPE À CHALEUR DE PISCINE Inverter 26 35 ...
Page 47: ... 43 5 3 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Inverter 26T 35T ...
Page 64: ... 60 2 Afmeting Dimension Model Inverter 7 10 Model Inverter 14 ...
Page 65: ... 61 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 73: ... 69 5 Elektrische bedrading 5 1 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 7 10 14 17 21 ...
Page 74: ... 70 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 26 35 ...
Page 75: ... 71 5 3 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Inverter 26T 35T ...
Page 92: ... 88 2 Ausmaße Model Inverter 7 10 Model Inverter 14 ...
Page 93: ... 89 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 102: ... 98 5 2 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Inverter 26 35 ...
Page 103: ... 99 5 3 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Inverter 26T 35T ...
Page 121: ... 117 2 Wymiary Model Inverter 7 10 Model Inverter 14 ...
Page 122: ... 118 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 131: ... 127 5 2 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Inverter 26 35 ...
Page 132: ... 128 5 3 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Inverter 26T 35T ...
Page 150: ... 146 2 Dimension mm Model Inverter 7 10 Model Inverter 14 ...
Page 151: ... 147 Model Inverter 17 Model Inverter 21 26 26T 35 35T ...
Page 160: ... 156 5 2 SWIMMINGPOOL VARMEPUMPE WIRING DIAGRAM Inverter 26 35 ...
Page 161: ... 157 5 3 SWIMMINGPOOL VARMEPUMPE WIRING DIAGRAM Inverter 26T 35T ...
Page 175: ......
Page 176: ...A0111HYI04 ...