- 31 -
8. Troubleshooting
8.1 Error code display on LED wire controller
Malfunction
Error code
Reason
Solution
Inlet water temperature
sensor failure
PP1
The sensor in open or short
circuit
Check or change the sensor
Outlet water temperature
sensor failure
PP2
The sensor in open or short
circuit
Check or change the sensor
Heating condenser
sensor failure
PP3
The sensor in open or short
circuit
Check or change the sensor
Gas return sensor failure
PP4
Connect some wire wrongly on
gas return sensor position
Confirm there is nothing on this
point, restart the machine
Ambient temperature
sensor failure
PP5
The sensor in open or short
circuit
Check or change the sensor
Temperature difference
between water inlet and
outlet is too much
PP6
Water flow volume not
enough ,water pressure
difference is too low
Check the water flow volume or
water jammed or not
Cooling outlet water
temperature is too low
PP7
Water flow volume is not
enough
Check the water flow or water
system is jammed or not
First grade antifreeze
protection in Winter
PP7
Ambient temperature or water
inlet temperature is too low
Water pump will run
automatically for first grade
antifreeze
Second grade antifreeze
protection in Winter
PP7
Ambient temperature or water
inlet temperature is too low
Heat pump will start heating for
second grade antifreeze
Cooling condenser
sensor failure
PP8
Connect some wire wrongly on
gas return sensor position
Confirm there is nothing on this
point, restart the machine
High pressure protection
EE1
1. Refrigerant is too much
2. Air flow is not enough
1. Discharge redundant
refrigerant from HP gas
system
2. Clean the air exchanger
Low pressure protection
EE2
1. Refrigerant is not enough
2. Water flow is not enough
3. Filter jammed or capillary
jammed
1. Check if there is any gas
leakage ,re-fill the
refrigerant
2. Clean the air exchanger
3. Replace the filter or
capillary
Flow switch closed
EE3 or "ON" Low water flow, wrong flow
direction, or flow switch failure.
Check if the water flow is
enough and flow in right
direction, or else the flow switch
could be failed.
Power supply
connections wrong (for 3
phase unit)
EE4
Wrong connection or lack of
connection
Check the connection of power
cable
Inlet and outlet water
temperature difference
malfunction
EE5
Water flow volume is not
enough ,water pressure
difference is too low
Check the water flow rate ,or
water system is jammed or not
Communication failure
EE8
Wire connection is not good
Check the wire connection
Summary of Contents for 7018522
Page 12: ... 11 2 Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Page 15: ... 14 3 5 Typical arrangement Note This arrangement is only an illustrative example ...
Page 21: ... 20 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 5 7 10 ...
Page 22: ... 21 5 2 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 13 ...
Page 23: ... 22 5 3 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 18 22 ...
Page 24: ... 23 5 4 SWIMMING POOL HEAT PUMP WIRING DIADRA Hydro Pro 26 ...
Page 30: ... 29 7 3 How to know the current status ...
Page 34: ... 33 9 Exploded Diagram and Maintenance 9 1 Exploded Diagram Model 7 kw ...
Page 43: ... 42 2 Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Page 53: ... 52 5 2 SCHEMA DE CABLAGE DE POMPE À CHALEUR DE PISCINE Hydro Pro 13 ...
Page 54: ... 53 5 3 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Hydro Pro 18 22 ...
Page 55: ... 54 5 4 SCHEMA DE CABLAGE DE LA POMPE À CHALEUR DE PISCINE Hydro Pro 26 ...
Page 61: ... 60 7 3 Comment savoir les états actuels ...
Page 65: ... 64 9 Schéma eclaté et entretien 9 1 Schéma eclaté Modèle 7 kw ...
Page 74: ... 73 2 Afmeting Dimension Hydro Pro 5 7 10 Hydro Pro 13 ...
Page 83: ... 82 5 Elektrische bedrading 5 1 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 5 7 10 ...
Page 84: ... 83 5 2 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 13 ...
Page 85: ... 84 5 3 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 18 22 ...
Page 86: ... 85 5 4 ZWEMBAD WARMTEPOMP BEDRADING SCHEMA Hydro Pro 26 ...
Page 92: ... 91 7 3 Hoe de huidige status te weten te komen ...
Page 105: ... 104 2 Ausmaße Hydro Pro 5 7 10 Hydro Pro 13 ...
Page 115: ... 114 5 2 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 13 ...
Page 116: ... 115 5 3 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 18 22 ...
Page 117: ... 116 5 4 VERKABELUNGSDIAGRAMM DER SCHWIMMBECKEN WÄRMEPUMPE Hydro Pro 26 ...
Page 123: ... 122 7 3 Den aktuellen Status abrufen ...
Page 146: ... 145 5 2 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 13 ...
Page 147: ... 146 5 3 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 18 22 ...
Page 148: ... 147 5 4 ДИАГРАММА ПРОВОДКИ ТЕПЛОВОГО НАСОСА ДЛЯ ПЛАВАТЕЛЬНОГО БАССЕЙНА Hydro Pro 26 ...
Page 154: ... 153 7 3 Как узнать текущий статус ...
Page 176: ... 175 5 2 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 13 ...
Page 177: ... 176 5 3 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 18 22 ...
Page 178: ... 177 5 4 SCHEMAT OKABLOWANIA POMPY GRZEWCZEJ DO BASENOW KĄPIELOWYCH Hydro Pro 26 ...
Page 183: ... 182 Należy zwrócić uwagę że ...