background image

HL-20210202  

Hydraloop Installation Manual   

 

 

 

14 

7.

 

Commissioning & Initial startup of the Hydraloop unit 

 

The commissioning should be performed by an accredited Hydraloop Partner that is trained to commission 

the Hydraloop unit. 

 

Commissioning steps: 

 

1.

 

Open external back up water source (tap or rainwater). Be sure the water pipe is rinsed before 

connecting to the Hydraloop unit so there is no dirt entering the float valve and Hydraloop unit, 

because this could damage the float valve, electric valves and the water pump. 

-

 

The small water tank on the lower left side should fill with water and the float valve should close 

when the maximum water level in the tank is reached. 

 

2.

 

Switch Hydraloop power switch on 

-

 

This start up procedure takes about 2 minutes.  

-

 

After this, please flush each toilet after each other in the building once, to push air out of the 

pipes.  

-

 

The Hydraloop unit will now only supply backup water to the house because at this stage the 

Hydraloop unit is not yet activated for recycling. The LED light on the front plate will be green. 

You can now check all connections to and from the Hydraloop unit for leaks.  

 

3.

 

WiFi setup: After the Hydraloop unit is switched on, it will automatically create a WiFi network 

showing a number (looks like 00:AB:00:AB:11)  

-

 

elect this Hydraloop WiFi network, that shows the long number, on your smart phone, tablet or 

computer (device) and enter the password: PASSWORD 

-

 

Check if your device is connected to the Hydraloop WiFi network (with the long number). 

-

 

Open an internet browser on your device and enter the 

URL 192.168.4.1. A page will open.  

-

 

Enter the existing WiFi network of the house/building 

that you want the Hydraloop unit to connect with, and 

enter the password belonging to this WiFi network on the 

page that is displayed and press ‘Submit’. The Hydraloop 

unit will now connect with this local WiFi network. Note: 

Spaces, commas, capitals etc. all should be entered 

correctly. 

 

Note: If the WiFi network does not have a password leave this 

field blank. 

 

4.

 

Enter/scan Hydraloop ID with Hydraloop App: 

-

 

Download and open the Hydraloop app on a smartphone (IOS or Android). Go to ‘settings, 

installation, enter/scan Hydraloop ID’.  

-

 

Enter the serial number of the Hydraloop unit that is printed on the Hydraloop Data Plate that is 

attached on the right hand top of the Hydraloop unit,  

-

 

or press ‘scan barcode’ and scan the bar code that is visible on the same Hydraloop Data Plate 

that is attached on the right hand top of the Hydraloop unit.  

-

 

After the information is entered correctly the central server at Hydraloop Systems B.V. will 

connect to this specific Hydraloop unit and will perform a brief system check.  

5.

 

Installers Initial Setup: For the initial setup the installer needs to press ‘Setup Hydraloop’ and enter 

the ‘installers code’. This will give access to the ‘setup’ section of the App.  

-

 

(if you do not have the installers code please contact Hydraloop Systems B.V.) 

Summary of Contents for H150

Page 1: ...Hydraloop H350 H300 H600 Installation manual ...

Page 2: ...vice Read this manual before using the product and keep it in a safe place for future reference To ensure safe and proper operation we recommend regular maintenance of the product Our Service and customer service organization can help with this We hope you will enjoy the product for many years to come ...

Page 3: ... considerations 9 6 2 Installation preparation 10 6 3 Front plate removal 10 6 4 Hydraloop wall mounting instructions 10 6 5 Hydraloop greywater inlet installation 11 6 6 Using a lift pump 11 6 7 Water in outlets 12 6 8 Hydraloop wastewater outlet installation 13 7 Commissioning Initial startup of the Hydraloop unit 14 8 Startup time 16 9 Potable water backup backflow prevention 16 10 Plumbing bac...

Page 4: ...s installers to avoid dangerous situations Always disconnect the Hydraloop from the mains before servicing or maintenance ATTENTION After servicing the Hydraloop the installation should always be checked for leakages 1 2 Recommendations ATTENTION The Hydraloop should only be placed indoor with an ambient temperature between 14 35 C 57 95 F The Hydraloop should never be placed in direct sunlight Th...

Page 5: ... 1 3 2 Installer The installer is responsible for the installation and initial commissioning of the Hydraloop device The Hydraloop device should always be installed according the local legislation and standards Perform initial commissioning and necessary checks Explain the installation to the user Hand over all manuals to the user 1 3 3 User To ensure optimal functioning of the Hydraloop device pl...

Page 6: ...led water outlet to feed the toilet cisterns a second recycled water outlet for feeding the laundry machine a third recycled water outlet to use for the garden in addition to recycling bathing water 50 of the laundry water can be recycled by the Hydraloop Product availability may vary by state or country It is not allowed to feed the Hydraloop unit with water from hand basins dishwashers kitchen s...

Page 7: ...pallet leave it strapped on the wooden transportation plate and the unit can be moved with a 2 wheel trolley Only when it is near its final position then remove the foil and carefully lift the unit from the plate and place it at its final position Transportation of Hydraloop H300 1x Hydraloop H300 on HL transport plate Transport upright System individually secured to HL transport plate with strapp...

Page 8: ...ndry machine recycle option is installed No washbasins kitchen sinks dishwasher may be connected Connect all separated greywater pipes from shower and bathtubs via a single 2 pipe to the 1 5 inlet on the top of the Hydraloop unit if necessary via a lift pump Hydraloop has a built in overflow facility no additional connection to the sewer is required The 50mm 2 greywater feed tube from the shower b...

Page 9: ...Connect incoming greywater to the inlet on the top in combination with lift pump if necessary Ch 6 5 6 6 5 Connect backup water inlet connection Ch 6 7 6 Connect Hydraloop recycled water outlet connections Ch 6 7 7 Connect Hydraloop wastewater outlet to sewer Ch 6 7 and 6 8 8 Plug 100 240V power cord into wall socket 9 Run the commissioning test using the Hydraloop App Ch 7 6 1 Installation consid...

Page 10: ...achine and greywater from showers flows direct to the sewer until the Hydraloop unit is installed More information regarding installation preparation can be found in our FACT SHEET Have your building Recycle Ready 6 3 Front plate removal Remove the stainless steel front plate using a lever on the lower side of the front plate to carefully lift the stainless plate up The plate is holding its positi...

Page 11: ... machine an appropriate lift pump has to be installed to pump the greywater from the source up into the Hydraloop system If a Hydraloop unit is equipped with the laundry machine water recycle option the ideal place for installation would be close to the laundry machine so that the laundry machine lift pump can be placed next or close to the laundry machine itself If the laundry machine is placed o...

Page 12: ...ize metric Thread type Additional information Greywater supply 1 5 40 mm Into feed channel 1 Backup water supply 1 2 male Min Flow 4 5 Gallon 20 liters p m Output connection Size imperial Size metric Thread type Additional information 2 Garden pool supply 1 2 Connect to flexible hose 3 Toilet supply 1 2 male Connect to flexible hose 4 Laundry machine supply optional 1 2 male Connect to flexible ho...

Page 13: ...npipe below the Hydraloop unit has to be connected to the sewer with PVC eccentric adapter ring or rubber reducing sleeve trough the floor first image or backwards to the wall second image Hydraloop drainpipe connected to sewage by using reducing sleeve A backwards connection to the sewage system Rubber reducing sleeve ...

Page 14: ...e tablet or computer device and enter the password PASSWORD Check if your device is connected to the Hydraloop WiFi network with the long number Open an internet browser on your device and enter the URL 192 168 4 1 A page will open Enter the existing WiFi network of the house building that you want the Hydraloop unit to connect with and enter the password belonging to this WiFi network on the page...

Page 15: ... the Hydraloop normally performs for treatment in about 15 minutes This test should always be performed at installation and after replacement of parts It is necessary to do a test routine to check for possible damage caused by transportation of the unit a Open the Hydraloop front plate by lifting it from the floor up and then you can move it upwards and set it aside so all tanks and internal parts...

Page 16: ...ll automatically switch over to offer recycled water to the toilets laundry machine and or garden 9 Potable water backup backflow prevention In the event there is not enough recycled water available the system will automatically switch to back up water potable or rainwater As soon as new recycled water is available the Hydraloop unit will automatically switch to supply recycled water The Hydraloop...

Page 17: ...rything in house will function as usual but no recycled water will be distributed as a precaution The visual alarm light on the Hydraloop front plate will blink red 4 times per minute indicating an abnormal situation a warning message is sent via the WiFi connection to the Hydraloop monitoring server and to the customers Hydraloop App and an audible beep as well will sound 4 times per minute see m...

Page 18: ...d or limited If you need assistance call your Hydraloop dealer or contact Hydraloop technical support via email support hydraloop com or phone on number 31 88 100 3500 EU 1 414 89 500 21 USA 13 Maintenance We recommend a check performed by a Hydraloop accredited installer once every two years This check contains the following elements Descale the Hydraloop unit with a citric acid solution to desca...

Page 19: ...w minimal 20 lit 4 5 gal per minute pressure minimal 2 bar 29 Psi Power supply 100 240V 20W 24V internal Expected power consumption 200 kWh year Average recycled water quality Hydraloop Residential water recycling products are certified to NSF ANSI standard 350 CBDO5 mg L 10 TSS mg L 10 Turbidity NTU 5 E coli MPN 100mL 14 PH SU 6 0 9 0 Noise level 44 dB Data Plate Service Label The Hydraloop unit ...

Page 20: ...he right to change the specifications stated in this document Hydraloop products are protected by patents and patents pending The Hydraloop brand name is a registered trademark Hydraloop Inc Global Water Center 247 W Freshwater Way Suite 210 Milwaukee WI 53202 United States of America 1 414 89 500 21 Hydraloop Systems B V Wetsus Building Water Campus Oostergoweg 9 8911 MA Leeuwarden Netherlands 31...

Reviews: