13 Technical specifications
Display range
Display
4-digit 7-segment LED display, red, height of digits 14.2 mm
3 LEDs for active sensor
4 LEDs for switching relays
Display range
- 999..9999 (adjustable by user)
Display units (of measurement) with background lighting °C,°F, %
(cut required unit label from sheet and slide it into the slot
on the side)
Input data
Analogue signal input(s)
Measuring range
4 .. 20 mA, sequential (HLB compatible)
Accuracy class
± 0.5 % at 25 °C
Output data
Analogue output
adjustable : 4 .. 20 mA, Ohmic resistance 400
O
or
0 .. 10 V, Ohmic resistance 2 k
O
Accuracy of the analogue output
± 0.5 % at 25 °C
Rise time
70 ms
Switching outputs
Type
4 relays each with separate common supply
Switching voltage
0.1 .. 250 VAC
Switching current
9 mA .. 2 A
Switching capacity
400 VA, 50 W ((for inductive loads, use varistors)
Life expectancy of the switching contacts
20 million at minimum load
1 million at nominal load
Reaction time (with switching delay = 0 ms)
approx. 20 ms
Setting range of the switching points
1.5 .. 100 % of the pre-set display range
Setting range of the switching hystereses
(switch-back points)
0.5 .. 99 % of the pre-set display range
Switching window upper switch point
2.25 .. 99 % of the pre-set display range
Switching window lower switch point
1.5 .. 98.24 % of the pre-set display range
Interface Serial
interface
RS232
Baud rate 19.200 Bauds – 8 data bits – 1 start and stop bit
– no parity – no handshake
Ambient conditions
Nominal temperature range
0 .. + 50 °C
Operating temperature range
0 .. + 50 °C
Storage temperature range
- 40 .. + 80 °C
- mark
EN 61000 – 6 –1 / 2 / 3 / 4
Other data
Housing
Control panel housing 96 x 48 x 109 mm
Control panel cut-out 92 (+0.8) x 45 (+0.6) mm
Front panel thickness 1.25.. 15 mm
Maximum installation depth 121 mm
Electrical connections
Supply voltage: plug-in terminal block, 2 pole, RM 5.08
Inputs / outputs: plug-in terminal block, 11 pole, RM 3.5
Relays: plug-in terminal block 6 pole, RM 5.08
Max. cross section of the connections 1.5 mm² for inputs /
outputs
Max. cross section of the connections 2.5 mm² for supply
voltage and relays
Supply voltage
85 .. 265 VAC 50 / 60 Hz
or
12 .. 32 VDC
Current consumption: without sensor
HDA 5500-0-2-AC-006
HDA 5500-0-2-DC-006
15 VA for 85 .. 230 VAC
280 mA max. for 24 VDC
Supply of the measurement transmitter
12
±
1 % VDC max. 20 mA per analogue input
Protection class to DIN 40050
IP 20
Reverse polarity protection of the supply voltage,
excess voltage, override protection
provided
Weight approx.
320
g